18
80A model (default)
Setting range is from 1 A to 140A.
Increment of each click is 1A.
13
Maximum
AC
charging current
30A model (default)
Setting range is from 1A to 60A.
Increment of each click is 1A.
14
Battery type
AGM (default) Flooded
GEL LEAD
Lithium Ion User-Defined
If "User-Defined" or “LI” is selected, battery charge voltage and
low DC cut-off voltage can be set up in program 17, 18 and 19.
17
Bulk charging voltage
(C.V voltage)
48V model default setting: 56.4V
If self-defined is selected in program 14, this program can be set
up. Setting range is from 48.0V to 58.4V for 48Vdc model.
Increment of each click is 0.1V
18
Floating
charging
voltage
48V model default setting: 54.0V
If self-defined is selected in program 14, this program can be set
up. Setting range is from 48.0V to 58.4V for 48Vdc model.
Increment of each click is 0.1V
19
Low
DC
cut
off
battery voltage setting
48V model default setting: 40.8V
If self-defined is selected in program 14, this program can be set
up. Setting range is from 40.0V to 48.0V for 48Vdc model.
Increment of each click is 0.1V. Low DC cut-off voltage will be
fixed to setting value no matter what percentage of load is
connected.
20
Battery
stop
discharging
voltage
when AC is available
Available options for 48V models:
46.0V (default)
Setting range is from 44.0V
to 58.0V.
Increment of each click is