9
5. Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may
cause AC short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because
it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage
occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent
this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay
function before installation. Otherwise, this inverter/charger will trig overload fault and cut off
output to protect your appliance but sometimes it still causes internal damage to the air
conditioner.
PV Connection
CAUTION
: Before connecting to PV modules, please install a DC circuit breaker or DC isolator
of appropriate size between inverter and PV modules.
WARNING!
All wiring must be performed by a qualified person.
WARNING!
It's very important for system safety and efficient operation to use appropriate cable
size for PV module connection.
Model
Typical Amperage
Cable Size
Torque
4048/60A
5048/60A
60A
8 AWG
1.4~1.6Nm
4048/80A
5048/80A
80A
6 AWG
2.0~2.4Nm
PV Module Selection:
When selecting PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV array can not exceed 145Vdc in the coldest condition.
2. Open circuit Voltage (Voc) of PV array needs to be higher than minimum battery voltage
Solar Charging Mode
INVERTER MODEL
4048/60A 5048/60A
4048/80A 5048/80A
Max. PV Array Open Circuit Voltage
145Vdc
PV Array MPPT Voltage Range
64~130Vdc
Min. battery voltage for PV charge
34Vdc
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors
2. Check correct polarity of connection from PV array to PV input