17
battery. If the battery voltage is higher than the
setting point in program 21, the solar energy will
supply to the load and recharge the battery.
Solar energy provides power to the loads as first
priority
If the battery voltage is lower than the setting in
point 20, solar energy will not supply power to the
load, it will only charge the battery. If the battery
voltage is higher than the setting in point 20, solar
energy will supply to the load and recharge the
battery.
06
Overload bypass:
The
unit
will
transfer
to
line
mode if overload
occurs in battery
mode.
Bypass disabled
Bypass enabled (default)
07
Auto restart when
overload occurs
Restart disabled
Restart enabled
08
Auto restart when
over
temperature
occurs
Restart disabled
Restart enabled
10
Charger
source
priority:
To
configure charger
source priority
If this inverter/charger is working in Line, Standby or Fault mode, charger
source can be programmed as below:
Solar first
Solar energy will charge battery as first priority.
AC will charge the battery only when solar energy
is not available.
Solar and “AC in”
Solar energy and AC will charge battery at the
same time.
Only Solar
Solar energy will be the only source to charge the
battery
If this inverter/charger is working in Battery mode or Power saving mode,
only solar energy can charge the battery. Solar energy will charge battery if it's
available and sufficient.
11
Maximum total
charging current:
Solar and AC input
60A model (default)
Setting range is from 1 A to 120A.
Increment of each click is 1A
.