Parameters
Filtering
The tension display and all 3 analog outputs have a separate low pass filter. The filter response
can be set from 100 Hz to 0.01 Hz.
Parameter #
Description
Units
Default
Range
P.02
Tension display filter frequency
Hertz
3
{00.01, 99.99}
P.03
0 to 10V output filter frequency
Hertz
40
{00.01, 99.99}
P.04
4 to 20mA output filter frequency
Hertz
40
{00.01, 99.99}
P.05
0 to1mA output filter frequency
Hertz
40
{00.01, 99.99}
Analog output scaling
Each analog output’s output values for zero tension and maximum tension can be set by the
following parameters.
Parameter #
Description
Units
Default
Range
P.06
Sets the 0 to 10V output voltage when
the tension is 0.
volts
0
{00.00, 10.00}
P.07
Sets the 0 to 10V output voltage when
the tension is equal to maximum tension
volts
10
{00.00, 10.00}
P.08
Sets the 4 to 20mA output current when
the tension is 0.
Allows changing to a 0 to 20 mA output
milliamps
4
{00.00, 20.00}
P.09
Sets the 4 to 20mA output current when
the tension is equal to maximum tension
milliamps
20
{00.00, 20.00}
P.10*
Sets the 0 to 1mA output current when
the tension is 0
volts
0
{00.00, 10.00}
P.11*
Sets the 0 to 1mA output current when
the tension is equal to maximum tension
volts
10
{00.00, 10.00}
* The voltage value entered in P.10 and P.11 represents the current value in milliamps when divided by 10.