31
Controllo per i-32V5 MIDI
Air/water inverter chillers and heat pumps with axial fans
Register
Format
Bit
R/W
Range
Name
Description
Note
951
BOOL
1
R
-
ALARM - E18
High temperature
9
ALARM - E26
* Thermal pump 2
11
ALARM - E41
Incongruent temperatures
12
ALARM - E42
Insufficient heat exchange
13
ALARM - E50
high temperature domestic hot wa
-
ter storage tank
14
ALARM - E101
Gi module disconnected
952
BOOL
0
R
-
ALARM - E611
Inlet water probe
1
ALARM - E621
Outlet water probe
2
ALARM - E631
Intake temperature
3
ALARM - E641
Exhaust temperature
4
ALARM - E651
Outside temperature
5
ALARM - E661
Probe 6
If active
6
ALARM - E671
Probe 7
If active
7
ALARM - E681
Probe 8
If active
8
ALARM - E691
low pressure transducer
9
ALARM - E701
high pressure transducer
10
ALARM - E711
Probe 11
If active
11
ALARM - E612
*module Gi - Probe 1
If active
12
ALARM - E622
*module Gi -Probe 2
If active
13
ALARM - E632
*module Gi - Probe 3
If active
14
ALARM - E642
*module Gi - Probe 4
If active
15
ALARM - E652
*module Gi - Probe 5
If active
953
BOOL
0
R
-
ALARM - E662
*module Gi - Probe 6
If active
1
ALARM - E672
*module Gi - Probe 7
If active
2
ALARM - E682
*module Gi - Probe 8
If active
3
ALARM - E692
*module Gi - Probe 9
If active
4
ALARM - E702
*module Gi - Probe 10
If active
5
ALARM - E712
*module Gi - Probe 11
If active
954
BOOL
1
R
-
ALARM- E801
Inverter link 1
2
ALARM - E802
*Inverter link 2
4
ALARM - E851
Hardware fault inverter 1
5
ALARM - E852
*Hardware fault inverter 2
7
ALARM - E861
Overcurrent inverter 1
8
ALARM - E862
High temperature inverter 1
10
ALARM - E871
Bad voltage inverter 1
11
ALARM - E872
*High temperature inverter 2
13
ALARM - E881
Bad voltage inverter 1
14
ALARM - E882
*Bad voltage inverter 2
955
BOOL
0
R
-
ALARM - E891
Phase sequence inverter 1
1
ALARM - E892
*Phase sequence inverter 2
3
ALARM - E901
Model error inverter 1
4
ALARM - E902
*Model error inverter 2
6
ALARM - E911
Overload error inverter 1
7
ALARM - E912
*Overload error inverter 2
9
ALARM.- E921
Overcurrent PFC inverter 1
10
ALARM - E922
*Overcurrent PFC inverter 2
12
ALARM - E931
Internal communication error invert
-
er 1
13
ALARM - E932
*Internal communication error
inverter 2
15
ALARM - E941
Fault PFC inverter 1
956
BOOL
0
R
-
ALARM - E942
*Fault PFC inverter 2
2
ALARM - E951
Probe error inverter 1
3
ALARM - E952
*Probe error inverter 2
5
ALARM - E961
Abnormal condition inverter 1
6
ALARM - E962
*Abnormal condition inverter 2
8
ALARM - E971
EEPROM inverter 1
9
ALARM - E972
*EEPROM inverter 2
(*) if present