29
Controllo per i-32V5 MIDI
Air/water inverter chillers and heat pumps with axial fans
Alarm code
DESCRIPTION
Block
E042
Insufficient heat exchange alarm
Macchine/Sanitary
E050
High DHW tank temperature alarm
-
E611
Water inlet probe failure
Machine
E621
Water outlet probe failure
Machine
E631
Compressor suction probe failure
Machine
E641
Compressor discharge probe failure / high pressure switch intervention
Machine
E651
External air / fan thermal probe failure
Machine
E661
DHW probe failure (ST6)
Machine
E671
Fault in remote plant probe (ST7)
Machine
E691
Low pressure transducer failure
Machine
E701
High pressure transducer failure
Machine
E711
Fault in voltage input 0-10V DC
Machine
E801
Inverter communication timeout
Compressor
E851
Inverter hardware problem
Compressor
E861
Motor current too high
Compressor
E871
High inverter heatsink temperature
Compressor
E881
Supply voltage out of limits (DC bus)
Compressor
E891
Compressor not connected
Compressor
E901
Wrong compressor model
Compressor
E911
Overload protection
Compressor
E921
PFC/POE overcurrent
Compressor
E931
Internal communication error
Compressor
E941
PFC fault
Compressor
E951
Heatsink and/or ambient temperature sensor fault
Compressor
E961
Abnormal condition
Compressor
E971
EEPROM error
Compressor
24. MODBUS VARIABLES
The control has the following modbus configuration by default:
•
Baud rate: 9600
•
Parità: EVEN
•
Data bit: 8
•
Stop bit: 1
•
Device ID: 1
To configure the Modbus communication according to your requirements, you must modify the following parameters:
Parameter
VALUE
Function
H124
0
Baud rate 4800 bit/s
1
Baud rate 9600 bit/s
2
Baud rate 19200 bit/s
3
Baud rate 38400 bit/s
H125
0
Parity NONE e stop bit 2
1
Parity ODD e stop bit 1
2
Parity EVEN e stop bit 1
3
Parity NONE e stop bit 1
H126
1 ÷ 120
Serial address (Device ID)
The following table lists the Modbus registers of the control:
Register
Format
Bit
R/W
Range
Name
Description
Note
1
INT
-
R
-
Data version
Firmaware version
2
INT
-
R
-
Firmware release
3
BYTE (H)
-
R
-
Firmware sub-release
BYTE (L)
-
R
-
Firmware creation day
4
BYTE (H)
-
R
-
Firmaware creation month
BYTE (L)
-
R
-
Firmware creation year
10
BOOL
0
R
-
Digital inputs
ID1 (flow swich)
1
ID 2
If active
2
ID 3 (on/off)
Active by default