background image

Controllo per i-32V5 MIDI

 Air/water inverter chillers and heat pumps with axial fans

24

In this way the heat pump will stop at the set point and the thermal jump, according to the set offset, will be borne by the boiler and/or the 

integration resistors.

19. 

ANTIFREEZE PROTECTION RESISTANCES (IF KA ACCESSORY IS PRESENT)

In units with KA accessory, this function is active from the factory configuration. The kit consists of an antifreeze heater positioned on the ex-

changer on the system side and a heating cable placed on the base of the unit. The installer can modify the operation of the antifreeze resistors 

by accessing the relative parameter menu:

PRG -> PSS -> PRG -> (enter installer password) -> PRG -> 

PAr

 -> PRG -> 

Fro

In heating mode, the water antifreeze heater is activated when the flow water temperature falls below 

r02 

(default r02 = 4,0°C), it is switched 

off when the temperature measured by the outlet water probe exceeds 

r02 + r06

 °C.

If the unit is in OFF or cooling mode, the water antifreeze heater is activated when the flow water temperature falls below 

r03

 (default r03 = 

4,0°C), it switches off when the temperature measured by the outlet water probe exceeds 

r03 + r06

 °C.

The crankcase heater, on the other hand, switches on when the outside air temperature falls below 3°C and switches off when the outside tem-

perature exceeds 5°C.

20. 

PARTIAL RECOVERY WITH DESUPERHEATER (IF DS ACCESSORY IS PRESENT)

This option allows to produce free hot water through partial heat recovery by desuperheating the gas from the compressor outlet. Units with 

DS accessory are equipped with a control expansion board, which allows the connection of a water temperature probe for DS to activate the call 

for recovery.

To enable operation, the following parameters must be set and the DS water temperature probe must be connected to terminal XC-121.1/12.2:

Parameter

VALUE

TERMINAL

Function

rE01

1

DS enabled in chiller mode

H17

6

XC-121.1/12.2

DS water temperature sensor

Recovery is enabled for operation if all the following conditions are met: 

• 

Compressor in operation

• 

Defrosting is not in progress and is not counting to enter defrost mode.

• 

There are no safety controls or restrictions active

The recovery call is activated if the temperature detected by the probe falls below the setpoint 

San – 4,0

°C and is deactivated when the tem-

perature exceeds the setpoint 

San

For more information see the technical bulletin of the unit.

NOTE: The partial recovery function does not activate if a defrost is in progress or if the countdown to enter defrost is in prog

-

ress.

21. 

LOGICS THAT CAN BE ACTIVATED WITH GI MODULE - SYSTEM MANAGEMENT (ACCES-

SORY)

If the System Management kit (optional) is present, a second control is located inside the electrical panel that acts as an I/O resource expansion 

module. With this second control it is possible to increase the number of logics that can be managed by the main control; in particular, these 

logics are used for system management and are listed below:

Parameter

VALUE

Function

H86

9

Compressor operation signalling

H87

24

Alarm signalling

H88

47

Machine block signalling

H89

31

*Plant season signalling

H90

21

*Defrosting in progress signalling

(*) only for heat pump units

22.  PERMITTED CONFIGURATION TABLES

Below is a table of user and installer parameters including all the permitted configurations. Not all the configurations listed can be selected at the 

same time. The values listed below may be subject to updates, in case of doubt please contact the company.

CAUTION:

• All operations with INSTALLER visibility must be carried out by QUALIFIED PERSONNEL.

• Values that differ from the default values may compromise the correct operation of the machine; if in doubt about the value 

to be set, contact the head office.

• The company excludes all contractual and extra-contractual liability for damage caused to persons, animals or things, due to 

installation, adjustment and maintenance errors, improper use or partial or superficial reading of the information contained in 

this manual.

• No responsibility is accepted for damage or malfunctions caused by changes to the factory parameters made by third parties 

who have not been expressly authorised to do so.

Summary of Contents for i-32V5C MIDI 0121

Page 1: ...the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained in this manual This manual...

Page 2: ...V5 MIDIAir water inverter chillers and heat pumps with axial fans 2 00 01 2021 EM AR First emission Rev Date Compiled Approved Note Code Serie MCO01040101001 00 Chillers and Inverter Air Water heat pu...

Page 3: ...9 OPERATING HOURS MENU oHr 10 4 10 LOG MENU HiSt 10 4 11 FIRWARE VERSION MENU Fir 10 4 12 USB MENU USB 10 4 12 1 FIRMWARE UPDATE UPdF 10 4 12 2 PARAMETERS UPDATE UPPA 10 5 SYSTEM RESOURCES 11 6 EDITIN...

Page 4: ...ON OR IN SUB STITUTION OF THE HEAT PUMP COMPRESSOR 19 18 8 OPERATION HEAT PUMP MODE 20 18 9 JOINT OPERATION I BRACKET 20 18 10 JOINT OPERATION II BRACKET 20 18 11 OPERATION IN SUBSTITUTION 20 18 12 OP...

Page 5: ...5 Controllo per i 32V5 MIDIAir water inverter chillers and heat pumps with axial fans 23 14 LACK OF VOLTAGE 28 23 15 UTILITIES BLOCK ALARM TABLE 28 24 MODBUS VARIABLES 29...

Page 6: ...cution due to dangerous electrical voltage Indicates important information that the operator has to follow in order to guarantee the correct operation of the unit in complete safety Also indicates som...

Page 7: ...activated and or modified at the same time Different values from the default values can compromise the correct operation of the unit in case of doubt on the value to set contact the company Only auth...

Page 8: ...u or to increase the parameter value DOWN key allows to move to a lower menu or to decrease the parameter value 4 1 2 LED Cooling mode LED is on if COOL or COOL SAN mode is selected Heating mode LED i...

Page 9: ...itary setpoint 48 0 25 60 C Coo2 Second Summer setpoint 18 0 Coo 25 C Hea2 Second Winter setpoint 35 0 25 Hea C If sanitary function is enabled see par 12 4 4 PASSWORD MENU PSS Enter the password for...

Page 10: ...you can read firmware version uEr revision rEu and sub revision SUb 4 12 USB MENU USB This menu appears after entering the installer password only if a USB key containing the relevant update files is...

Page 11: ...3 2 2 Remote on off Voltage free digital input Active function by default par 13 1 DI9 H53 XC 7 1 XC 7 2 0 Not set Voltage free digital input DO3 H81 XP 1 1 N XP 1 2 phase 22 System integration heate...

Page 12: ...put type 0 10 V default b20 1 for ratiometric input Correction calculation with input 0 10 V b20 0 With input at 0 Volt the current set point will be set Coo Hea b15 2 With 5 Volt input the set point...

Page 13: ...TING ON CALL BY TEMPERATURE CONTROLLER WITH PERIODIC ACTIVATION With P03 1 you can also configure the circulator to run periodically according to the following parameters P16 Periodic activation time...

Page 14: ...s with maintenance privilege PRG PSS PRG enter installer password PRG Press UP and DOWN simultaneously for 3 seconds It is possible to exit the system venting cycle manually by pressing the MODE ESC b...

Page 15: ...y time the compressor is switched on and off 10 1 SILENCED VENTILATION Configuring a digital input DI9 with parameter H53 25 it is possible to manage the function of silent ventilation management Para...

Page 16: ...er the display returns to show the water outlet temperature In heating mode before entering DHW mode the last value read by the flow probe of the heat pump is memorised Once the DHW temperature contro...

Page 17: ...ing the compressor start up phase the switch off is managed by the probe on the heat pump delivery In heating mode the call is active if the following conditions are verified Flow probe temperature He...

Page 18: ...tivated if the control temperature remains below the water set point Hea r11 C and the machine is in lockout due to the intervention of an alarm It switches off when the machine exits the alarm block...

Page 19: ...r r23 r23 0 default for boiler not used priority of resistor intervention r23 1 for boiler use on system only priority of resistor intervention r23 2 for boiler use only in DHW mode priority intervent...

Page 20: ...ntrolled by the flow probe of the heat pump 18 10 JOINT OPERATION II BRACKET If the outside temperature is between r28 and r08 the auxiliary heaters are enabled in combination with the heat pump in he...

Page 21: ...ter r16 minutes DHW integration resistence HEAT SAN SANITARY 0 1 1 Set the minutes 5 6 2 3 1 System DHW integration resistence HEAT HEAT SAN HEAT SANITARY 1 1 0 3 1 Boiler HEAT HEAT SAN HEAT SANITARY...

Page 22: ...m integration resistence 2 After r12 minutes heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set the minutes 0 2 5 1 3 1 Boiler 2 After r16 minutes heat pump HEAT SAN SANITARY 0 1 0 1 2 Set the minutes 2 3 5 6 0...

Page 23: ...egration resistance COOL SAN SANITARY 0 1 1 Set the minutes 0 1 2 3 4 5 6 2 3 Table 6 shows the behaviour of the plant and DHW integration heaters in all the operating modes of the unit TABLE 6 INTEGR...

Page 24: ...all the following conditions are met Compressor in operation Defrosting is not in progress and is not counting to enter defrost mode There are no safety controls or restrictions active The recovery ca...

Page 25: ...tal inputs N A 1 ID1 polarity inverted 2 ID2 polarity inverted 4 ID3 polarity inverted 8 ID4 polarity inverted 16 ID5 polarity inverted 32 ID6 polarity inverted 64 ID7 polarity inverted 128 ID8 polari...

Page 26: ...l between 2 periodi cal activations of the pump min 0 0 600 I See par 8 P17 Operating time of the pump in periodical mode sec 0 0 255 I See par 8 r02 Antifreeze heaters setpoint in heating mode C 4 3...

Page 27: ...inside the unit and must not be tampered with or bypassed in any way The flow switch is bypassed by the control for a period of 10 seconds from the start of the machine after the bypass time the stat...

Page 28: ...sing and is manual reset The alarm is not active for a bypass time of approximately 180 seconds from the start of the compressor In heating or DHW mode after the bypass time has expired the alarm is a...

Page 29: ...E911 Overload protection Compressor E921 PFC POE overcurrent Compressor E931 Internal communication error Compressor E941 PFC fault Compressor E951 Heatsink and or ambient temperature sensor fault Com...

Page 30: ...l 1 heat 4 Sanitary 0 off If active 1 running 5 7 Defrost status 0 inactive 1 starting 2 active 3 dripping 4 finished 253 C 10 R Transducer tempera tures evaporazione 254 C 10 R evaporation 305 ora R...