i-SHWAK V4
Inverter air/water chillers and heat pumps with wall-mounted indoor unit and remote condensing outdoor unit
32
14.3
INDOOR UNITS
TECHNICAL FEATURES
Unit
Model
MP / MPR
Indoor unit coupled with moto-condensing unit size:
kW
06
08
10
12
Circulator
Water flow (3)
m
3
/h
1,16
1,39
1,72
2,08
Available head pressure (3)
kPa
62,7
55,5
54
35,7
Nominal input power (3)
kW
0,075
0,09
Max. input power
kW
0,075
0,09
Max. input current
A
0,60
0,7
Energy Efficiency Index (EEI)
≤
0,21
≤ 0,23
Hydraulic circuit
Expansion vessel of technical plant side
L
8
8
Hydraulic plant flow/return connections
inch
1”M
1”M
Minimum additional water volume(12)
L
31
37
46
51
DHW-R circuit
(Only for MPR
models)
Maximum supplied flow rate for DHW side
L/min
40
40
Minimum water flow for start-up
L/min
3
3
Max. input power of circulator
kW
0,045
0,045
Max. input current of circulator
A
0,44
0,44
Energy Efficiency Index (EEI)
≤ 0,20
≤ 0,20
Hydraulic connections
inch
3/4”M
3/4”M
Refrigerant
circuit
Liquid side connection
inch
3/8” SAE
3/8” SAE
Gas side connection
inch
5/8” SAE
5/8” SAE
Noise level
Sound power L
w
MP / MPR (8)
dB(A)
32 / 35
38 / 39
Sound pressure at 1 m MP / MPR (14)
dB(A)
24 / 27
30 / 31
Sound pressure at 10m MP / MPR (14)
dB(A)
4 / 7
10 / 11
Dimensions and
weight
Dimensions of MP model (LxDxW)
mm
314×893×343
314×893×343
Dimensions of MPR model (LxDxW)
mm
450×893×343
450×893×343
Packaging dimensions (LxDxW) (13)
mm
1000x600x560
1000x600x560
Operating weight MP/MPR
kg
36 / 47
36 / 47
Net weight MP/MPR
kg
25,5 / 34,5
25,7 / 34,7
Gross weight MP/MPR
kg
34 / 43
34 / 43
TECHNICAL FEATURES
Unit
Model
MP / MPR
Indoor unit coupled with moto-condensing unit size:
kW
14
16
Circulator
Water flow (3)
m
3
/h
2,37
2,62
Available head pressure (3)
kPa
50,7
36,4
Nominal input power (3)
kW
0,140
0,140
Max. input power
kW
0,140
0,140
Max. input current
A
1,05
1,05
Energy Efficiency Index (EEI)
≤ 0,23
≤ 0,23
Hydraulic circuit
Expansion vessel of technical plant side
L
8
8
Hydraulic plant flow/return connections
inch
1”M
1”M
Minimum additional water volume(12)
L
69
88
DHW-R circuit
(Only for MPR
models)
Maximum supplied flow rate for DHW
side
L/min
40
40
Minimum water flow for start-up
L/min
3
3
Max. input power of circulator
kW
0,045
0,045
Max. input current of circulator
A
0,44
0,44
Energy Efficiency Index (EEI)
≤ 0,20
≤ 0,20
Hydraulic connection
inch
3/4”M
3/4”M
Refrigerant circuit
Liquid side connection
inch
3/8” SAE
3/8” SAE
Gas side connection
inch
5/8” SAE
5/8” SAE
Noise level
Sound power L
w
MP / MPR (8)
dB(A)
39 / 40
39 / 40
Sound pressure at 1 m MP / MPR (14)
dB(A)
31 / 32
31 / 32
Sound pressure at 10m MP / MPR (14)
dB(A)
11 / 12
11 / 12
Dimensions and
weight
Dimensioni (LxDxW) modello MP
mm
314×893×343
314×893×343
Dimensioni (LxDxW) modello MPR
mm
450×893×343
450×893×343
Packing dimensions (LxAxP) (13)
mm
1000x600x560
1000x600x560
Operating weight MP/MPR
kg
37 / 48
37 / 48
Net weight MP/MPR
kg
26 / 35
26 / 35
Gross weight MP/MPR
kg
35 / 44
35 / 44
(3) Heating:
Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C.
(8) Sound power level
Heating mode condition (3) measured value made according to UNI EN ISO 9614-2, as required for Eurovent certification.
(12) Calculated for a decrease of the plant water temperature with 10°C and including defrosting cycle maintained for 6 minutes. Minimum water volume to be
added to the plant circuit in a
ddition to that required for the plant side unit’s hyadraulic circuit.
(13) Dimensions of pallet are included.
(14) Sound pressure level at 1m and 10m away from the sound source obtained with internal measurements made in accordance with ISO 3744, in case of the
sound source located in free field positioned over a reflecting plane.
WARNING: The minimum temperature allowed for storing the units is 5°C.