i-SHWAK V4
Inverter air/water chillers and heat pumps with wall-mounted indoor unit and remote condensing outdoor unit
31
14.2
OUTDOOR UNITS
TECHNICAL DATA
Unit
Model i-SHWAK V4
06
08
10
12
Electrical data
Power supply
230V/1/50Hz
230V/1/50Hz
Max. Input power
kW
3,2
4,7
5,0
6,0
Max. starting current
A
8,5
12,9
13,7
16,6
Compressor
Type
Twin Rotary DC Inverter
Number
1
1
1
1
Refrigerant oil (type, quantity)
mL
ESTER OIL VG74, 670
ESTER OIL VG74, 1000
Fan motor
Type
DC Brushless Motor
Number
1
1
1
1
Refrigerant
Type
R410A
R410A
R410A
R410A
Rfrigerant quantity (7)
kg
2,18
2,03
3,9
3,9
Equivalent amout of CO
2
ton
4,55
4,2
8,1
8,1
Design pressure (high/low)
MPa
4,2 / 2,7
4,2 / 2,7
4,2 / 2,7
4,2 / 2,7
Refrigerant
piping
Liquid side connections
inch SAE
3/8”
3/8”
3/8”
3/8”
Gas side connections
inch SAE
5/8”
5/8”
5/8”
5/8”
Required minimum Refrigerant pipe length
m
3
3
3
3
Max. Refrigerant pipe length
m
30
30
30
30
Length for nominal capacity
m
5
5
5
5
Max. length with Standard refrigerant load
m
7
7
7
7
Additional refrigerant for every meter
exceeding the standard length (10)
g/m
20
20
20
20
Max. difference in level (9)
m
15 / 20
15 / 20
15 / 20
15 / 20
Noise level
Sound power (8)
dB(A)
62,0
62,5
63,0
63,5
Sound pressure at 1m / 10m (14)
dB(A)
54 / 34
54,5 / 34,5
55 / 35
55,5 / 35,5
Dimensions
and weight
Dimensions (LxDxW)
mm
925 x 785 x 380
925 x 785 x 380
1047 x 913 x 465
1047 x 913 x 465
Packing dimensions (LxDxW) (11)
mm
995 x 944 x 415
995 x 944 x 415
1120 x 1080 x 520
1120 x 1080 x 520
Operating weight
kg
62
62
83,5
83,5
Net/Gross weight
kg
62 / 70
62 / 70
83,5 / 90
83,5 / 90
TECHNICAL DATA
Unit
Model i-SHWAK V4
14
14T
16
16T
Electrical data
Power supply
230V/1/50Hz
400V/3P+N+T/50
Hz
230V/1/50Hz
400V/3P+N+T/50Hz
Max input power
kW
7,5
7,5
7,9
7,9
Max input current
A
31,8
10
34
10,6
Compressor
Type
Twin Rotary DC Inverter
Twin Rotary DC Inverter
Number
1
1
Refrigerant oil (type, quantity)
mL
ESTER OIL VG74, 1400
ESTER OIL VG74, 1400
Fan motor
Type
DC Brushless Motor
DC Brushless Motor
Number
2
2
Refrigerant
Type
R410A
R410A
Refrigerant quantity (7)
kg
4,9
5,1
Equivalent amout of CO
2
ton
10,2
10,6
Design pressure (high/low)
MPa
4,2 / 2,7
4,2 / 2,7
Refrigerant piping
Liquid side connections
inch
SAE
3/8”
3/8”
Gas side connections
inch
SAE
5/8”
5/8”
Required minimum Refrigerant pipe
length
m
3
3
Max. Refrigerant pipe length
m
30
30
Length for nominal capacity
m
5
5
Max. length with Standard refrigerant
load
m
7
7
Additional refrigerant for every meter
exceeding the standard length (10)
g/m
20
20
Max. difference in level (9)
m
20 / 25
20 / 25
Noise level
Sound pressure (8)
dB(A)
65,5
66,0
Sound pressure at 1m / 10m (14)
dB(A)
57,5 / 37,5
58 / 38
Dimensions and
weight
Dimensions (L×A×P)
mm
1060 x 1405 x 455
1060 x 1405 x 455
Packing dimensions (LxDxW) (11)
mm
1125 x 1675 x 690
1125 x 1675 x 690
Operating weight
kg
112,2
123
Net/Gross weight
kg
112,2 / 123,2
123 / 134
Operating conditions:
(7) Refrigerant charge valid until 5m of distance between indoor and outdoor units.
(8) Sound power level
Heating mode condition (3) measured value made according to UNI EN ISO 9614-2,
as required for Eurovent certification.
(9) Data for: Indoor unit is up and Outdoor unit is down / Indoor unit is down and Outdoor unit is up (in this case a siphon must be created each 5 m of the piping
length).
(10) Additional refrigerant for pipe dimensions coherent with the intended attacks
(11) Packaging height including the pallet: in particular, the pallet height for the models V4 06/08 is 117mm, for V4 10/12 is 126mm and for the models V4
14/14T/16/16T is 170m.
(14) Sound pressure level obtained with internal measurements made in accordance with ISO 3744, in case of the sound source located in free field positioned over
a reflecting plane.
The Power inputs include all components of the circuit such as fan motors, pumps, valves and controller, the test data is obtained according to EN 14511: 2013.
N.B. The data shown are only for indication and could be subject to change, please always refer to the technical labels on board unit.
WARNING: The minimum temperature allowed for storing the units is 5°C.