![Matelec FPC-30010 Owner'S Manual Download Page 6](http://html1.mh-extra.com/html/matelec/fpc-30010/fpc-30010_owners-manual_1739991006.webp)
6
Maximum Run and Alternation Mode
With
DIP Switch 3
set to “Off” the unit will alternate as usual each time a pump start condition occurs.
Additionally, the controller will automatically alternate pump duty if a pump has been running continuously for
30 minutes (maximum run timer)
Setting this DIP switch to “On” will cause the controller to operate in “Circulation Mode” where duty will only
alternate once the pump has run for 6 hours of accumulated time
.
Anti-seize Timer
With
DIP Switch 4
set to “On”, the Anti-seize timer wil automatically run the pumps for 10 seconds, every 7 days.
This pump operation will completely override all inputs including the low level (if enabled). This feature will only
run pumps that are set in Auto. This “Pump Run”, will alternate between Pump 1 and Pump 2. A pump that has
been locked out due to a fault will not run.
Manual Mode Timeout
With
DIP switch 5
set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it
automatically reverts to Auto.
Audible and Visual Alarm Test
By pressing the
Mute/Reset
button on the keypad continuously for a period of 5 seconds, the Strobe, Siren and
Indicator Lights will be powered up for inspection
Fault Reset
To reset all faults on the controller, press and hold the Mute/Reset button on the keypad continuously for a period
of 3 seconds until an acknowledgement beep is heard.
Pump Fault
A Pump Fault is indicated for two types of Faults. A Thermal Overload will be indicated by way of a steady Fault
Indicator light. A Prime Loss fault will be indicated by way of a flashing Fault Indicator Light. Both types of faults can
be reset by way of the Fault Reset button.
Level Alarms
A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light.
A Low Level/Low Pressure Alarm is indicated by way of a Flashing Level Alarm Light.
Auto Silencing Alarm Feature
The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatically
silence and enter “Chirp” mode. In Chirp Mode, the Audible Alarm will sound briefly (2 Seconds)
every 5 minutes
High Level Alarm Reset
With
DIP Switch 6
set to “Off”, the high level alarm will automatically reset once the high level input opens circuit.
The controller will also use the alternate high level alarm delay. Typically used for Storm Water applications. High
Level Alarm delay in this mode is 15 minutes.
Setting this DIP switch to “On”, will cause the high level alarm to remain active until the controller is reset. The
high level alarm will use the standard high level alarm activation delay. Typically used for Sewerage applications.
High Level Alarm delay in this mode is 5 minutes.