Matelec FPC-30010 Owner'S Manual Download Page 6

6

Maximum Run and Alternation Mode

With 

DIP Switch 3

 set to “Off” the unit will alternate as usual each time a pump start condition occurs.

Additionally, the controller will automatically alternate pump duty if a pump has been running continuously for 
30 minutes (maximum run timer)
Setting this DIP switch to “On” will cause the controller to operate in “Circulation Mode” where duty will only 
alternate once the pump has run for 6 hours of accumulated time

.

Anti-seize Timer

With 

DIP Switch 4

 set to “On”, the Anti-seize timer wil automatically run the pumps for 10 seconds, every 7 days. 

This pump operation will completely override all inputs including the low level (if enabled). This feature will only
run pumps that are set in Auto. This “Pump Run”, will alternate between Pump 1 and Pump 2. A pump that has
been locked out due to a fault will not run.

Manual Mode Timeout

With 

DIP switch 5

 set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it 

automatically reverts to Auto.

Audible and Visual Alarm Test

By pressing the 

Mute/Reset

 button on the keypad continuously for a period of 5 seconds, the Strobe, Siren and

Indicator Lights will be powered up for inspection

Fault Reset

To reset all faults on the controller, press and hold the Mute/Reset button on the keypad continuously for a period 
of 3 seconds until an acknowledgement beep is heard.

Pump Fault

A Pump Fault is indicated for two types of Faults. A Thermal Overload will be indicated by way of a steady Fault 
Indicator light. A Prime Loss fault will be indicated by way of a flashing Fault Indicator Light. Both types of faults can 
be reset by way of the Fault Reset button.

Level Alarms

A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light.
A Low Level/Low Pressure Alarm is indicated by way of a Flashing Level Alarm Light.

Auto Silencing Alarm Feature

The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatically
silence and enter “Chirp” mode. In Chirp Mode, the Audible Alarm will sound briefly (2 Seconds)
every 5 minutes

High Level Alarm Reset

With 

DIP Switch 6

 set to “Off”, the high level alarm will automatically reset once the high level input opens circuit.

The controller will also use the alternate high level alarm delay. Typically used for Storm Water applications. High 
Level Alarm delay in this mode is 15 minutes.

Setting this DIP switch to “On”, will cause the high level alarm to remain active until the controller is reset. The
high level alarm will use the standard high level alarm activation delay. Typically used for Sewerage applications.
High Level Alarm delay in this mode is 5 minutes.

Summary of Contents for FPC-30010

Page 1: ...AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Loss Steady Overload...

Page 2: ...Features WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Br...

Page 3: ...oller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Lo...

Page 4: ...el Standard configuration plus low level Start Stop High level and Low level Standard configuration plus Prime Loss enabled on Low level Input 1 Pressure Pumping configuration Lead Lag and Low pressur...

Page 5: ...d Note that after a high level is triggered the pumps will both run until the pump Start and Stop inputs are opened Typical operation for Mode D Low pressure switch set at say 200kPa Lag pump pressure...

Page 6: ...roller press and hold the Mute Reset button on the keypad continuously for a period of 3 seconds until an acknowledgement beep is heard Pump Fault A Pump Fault is indicated for two types of Faults A T...

Page 7: ...LE PUMP 1 ISOLATOR 20amp 2 POLE PUMP 2 ISOLATOR CONTACTOR 2 PUMP 2 DATA OUTPUT 2amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 12Vdc 240Vac INPUT 1 SWITCH INPUT 2 SWITCH I...

Page 8: ...to Automatic Pumping Mode The pump is set to Manual Pumping Mode To turn pump off DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER Dual Pump Controller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RE...

Reviews: