This controller can perform control functions for most Dual Pump pumping applications. It is more than likely that the 
control parameters have already been set up for your particular application however;  hereunder you will find details of 
the set up and configuration options. 
 
There are 6 DIP switches located on the lower side of the control module, which allow s for selecting “mode” and 
“feature”  options, as per the following table:  
 

Operation Selection Table

 

DIP Switch 

Position 

Function 

1/2 

Off/Off 

Mode A:

Off/On 

Mode B:

 

On/Off 

Mode C:

 

On/On 

Mode D:

 

Off  

On 

Off  

Anti-seize timer disabled 

On 

Anti-seize timer 10 seconds every 7 days enabled

 

Off  

When placed in Manual mode pump remains in Manual mode 

On 

When placed in Manual mode after 5 minutes, the pump will revert to Auto 

Off  

High Level alarm Automatically  resets upon open circuit of high level input.  
High level alarm has 15 Minute delay. 

On 

High level alarm can only  be reset  Manually . High level alarm has 5 minute 
delay. 

 

  

Mode A:  Standard configuration

Start/Stop/High level operation. When the pump start input is closed contact (triggered), the duty pump will be 

Standard typical float switch configuration (Start, Stop and High Level).
No low level. 

Standard configuration plus low level (Start, Stop, High level and Low 
level).
Standard configuration plus Prime Loss enabled, on Low level (Input 1)
Pressure Pumping configuration (Lead, Lag and Low pressure)

Operating pump alternates after 6 hours continuous running

Operating pump alternates each time a pump start is triggered, or after 30 
minutes continuous running.

turned on. The pump will remain on until both the pump start and pump stop inputs have turned off (open circuited). 
Upon high level both pumps will run until the pump stop input turns off.

In addition to this, there is a maximum idle timer, which will trigger a pump start condition, if either pump has not 
run for 4 hours, and the stop float contacts are closed. The pump will continue to run until the stop float contacts open. 
Input functions are as follows:

Mode B:  Standard Configuration plus Low Level Alarm 

As per Mode A, except it has an active Low Level input. The low level input must be closed, for pump start and pump 
stop inputs to function. The High level input however, will still override the low level and run both pumps. 
Input functions are as follows:

The basic logic on which a High or Low Level Alarm is determined, is set out in the Table A.

Input 

Function

Input 1  Low Level
Input 2  Pump Stop
Input 3  Pump Start
Input 4  High Level

Input 

Function

Input 1  Not Used
Input 2  Pump Stop
Input 3  Pump Start
Input 4  High Level

  

4

Summary of Contents for FPC-30010

Page 1: ...AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Loss Steady Overload...

Page 2: ...Features WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Br...

Page 3: ...oller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Lo...

Page 4: ...el Standard configuration plus low level Start Stop High level and Low level Standard configuration plus Prime Loss enabled on Low level Input 1 Pressure Pumping configuration Lead Lag and Low pressur...

Page 5: ...d Note that after a high level is triggered the pumps will both run until the pump Start and Stop inputs are opened Typical operation for Mode D Low pressure switch set at say 200kPa Lag pump pressure...

Page 6: ...roller press and hold the Mute Reset button on the keypad continuously for a period of 3 seconds until an acknowledgement beep is heard Pump Fault A Pump Fault is indicated for two types of Faults A T...

Page 7: ...LE PUMP 1 ISOLATOR 20amp 2 POLE PUMP 2 ISOLATOR CONTACTOR 2 PUMP 2 DATA OUTPUT 2amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 12Vdc 240Vac INPUT 1 SWITCH INPUT 2 SWITCH I...

Page 8: ...to Automatic Pumping Mode The pump is set to Manual Pumping Mode To turn pump off DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER Dual Pump Controller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RE...

Reviews: