Matelec FPC-30010 Owner'S Manual Download Page 3

3

1.  Controller enclosure must be 
     mounted in a vertical position.

2.  Ensure mounting method 

     does not compromise enclosure 
     weather proof rating.

3.  Ensure access to main isolator 

     is not restricted.

4.  Ensure cables/conduits 

     entering the panel have 
     mechanical protection and that 
     the penetrations are 
     sealed and do not compromise 
     the weather proof rating of the 
     enclosure.

MOUNTING

FRONT VIEW

SIDE VIEW

Top

Bottom

Top

Bottom

Mounting 
Frame/

Wall

CONNECTION

NOTE:

 Controller must be earthed and all electrical connections must be carried out by a suitably qualified 

            Electrician

OFF

  ON 

Dual Pump

Controller

PUMP 1

PUMP 2

AUTO

OFF

AUTO

OFF

MAN

MAN

MUTE/

RESET

PUMP ON

PUMP ON
FAULT

FAULT

LEVEL

ALARM

POWER

ON

DANGER - HIGH VOLTAGE

DO NOT REMOVE COVER.  AUTHORIZED PERSONS ONLY

Steady - Overload

Flash - Prime Loss

Steady - Overload

Flash - Prime Loss

Press and hold

for 3 secs to reset 

Steady - High Level

Flash - Low Level

PUMP 1

PUMP 2

240Vac

MAINS POWER

SUPPLY

    SUPPLY

High

Ac

tiv

e

Ac

tiv

e

Ne

ut

ra

l

INPUT SWITCHES

Level

Level

Level

Ne

ut

ra

l

Input 2

Input 3

Ea

rth

Ac

tiv

e

Ne

ut

ra

l

240Vac

12Vdc Connections

Note:

Applications, connect to "Start (Input 3)" terminals only, 

and NO

PU

M

Ea

rth

PU

M

Ea

rth

Input 4

Stop

Start

PUMP 1

PUMP 2

BLUE NOT

        REQUIRED

STOP/

LOW

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

START/

MEDIUM

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

STANDBY/

HIGH

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

SET THERMAL OVERLOADS TO SUIT PUMP

Summary of Contents for FPC-30010

Page 1: ...AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Loss Steady Overload...

Page 2: ...Features WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Br...

Page 3: ...oller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Lo...

Page 4: ...el Standard configuration plus low level Start Stop High level and Low level Standard configuration plus Prime Loss enabled on Low level Input 1 Pressure Pumping configuration Lead Lag and Low pressur...

Page 5: ...d Note that after a high level is triggered the pumps will both run until the pump Start and Stop inputs are opened Typical operation for Mode D Low pressure switch set at say 200kPa Lag pump pressure...

Page 6: ...roller press and hold the Mute Reset button on the keypad continuously for a period of 3 seconds until an acknowledgement beep is heard Pump Fault A Pump Fault is indicated for two types of Faults A T...

Page 7: ...LE PUMP 1 ISOLATOR 20amp 2 POLE PUMP 2 ISOLATOR CONTACTOR 2 PUMP 2 DATA OUTPUT 2amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 12Vdc 240Vac INPUT 1 SWITCH INPUT 2 SWITCH I...

Page 8: ...to Automatic Pumping Mode The pump is set to Manual Pumping Mode To turn pump off DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER Dual Pump Controller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RE...