Matelec FPC-30010 Owner'S Manual Download Page 5

5

Table A  

Input 1

   

Low Level

Input 2

 

Pump Stop

 

Input 3

Pump Start

 

Input 4

   

 

High Level

 

Pump
State

 

 

 

Alarm 

 

Closed 

Open/Closed

Open 

Open 

Off  

Closed 

Open/Closed 

Closed 

Open 

On 

Closed 

Open/Closed 

Closed 

Closed 

Both on  High level (after timeout)  

Closed 

Open/Closed 

Open 

Closed 

Both on  High level (after timeout)  

Open 

Open/Closed 

Open 

Open 

Off  

Open 

Open/Closed 

Closed 

Open 

Off 

Low level  

Open 

Open/Closed 

Open 

Closed 

Off  

Low level  

Open 

Open/Closed 

Closed 

Closed 

Both on  High level (after timeout)  

 

Mode C:  Standard Configuration plus Prime Loss

As per Mode A, except Input 1 is connected to a prime loss/flow switch. If at any stage, after pump start
or whilst a pump is running, the prime loss input closes, for a continuous 2 minute period, a fault is immediately
triggered for that pump and duty alternates. Input functions are as follows:

Input  

Function 

Input 1 

Prime Loss  

Input 2 

Pump Stop 

Input 3 

Pump Start 

Input 4 

High Level 

 

Mode D:  Pressure Pumping Configuration

Duty Pump:                                       Lead Pump
Standby Pump:                                 Lag Pump
Input functions are as follows:

 

 

 

Input  

Function

Input 1 

Not used 

Input 2 
Input 3 
Input 4 

If there is a low level alarm , then both pumps will be locked out until the alarm is manually reset. 
This lockout will only be overidden upon a high level condition where both the Pump Start and High
Level inputs are closed.

Note that after a high level is triggered, the pumps will both run until the pump Start and Stop 
inputs are opened.

Typical operation for Mode D

Low pressure switch (set at say 200kPa)

Lag pump pressure switch (set at say 350kPa)

Lead pump pressure switch (set at say 350kPa)

Pressure drops to 400kPA: Lead (for this cycle) Pump cuts in.

Pressure increases and Pump cuts out.

Cycle continues with duty (Lead and Lag) alternating between the two pumps.

If pressure drops to 350kPA, Lag Pump will cut in and remain running until Lead Pressure switch

opens circuit. Then duty alternates.

No faults are logged against the Lead Pump if the Lag Pump starts.

The controller has inbuilt timers for”Delayed” Start and Stop to obviate pump chatter. Upon Input 1

contact closure, the pump will not start (delay start) for 3 seconds and will not stop (minimum run time) 

for 30 seconds (or 33 seconds from close of Input contacts). This “run on” occurs even if Lead Pressure 

switch opens circuit during this initial period. If however run time exceeds 33 seconds, 

the pump will stop immediately upon “open circuit” occuring.

If the Lead Pressure Switch input closes circuit as well as the Low Pressure Switch input, both 
pumps will be turned on and the Low Pressure Timer will begin counting.If this condition exists for a 
period of 60 seconds, then both pumps are shut down and the system signals a level alarm. This 
would be typical of a Loss of Prime or Burst Main situation.

Pressure switches are normally Closed and Open on High pressure

Summary of Contents for FPC-30010

Page 1: ...AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Loss Steady Overload...

Page 2: ...Features WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Br...

Page 3: ...oller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY Steady Overload Flash Prime Lo...

Page 4: ...el Standard configuration plus low level Start Stop High level and Low level Standard configuration plus Prime Loss enabled on Low level Input 1 Pressure Pumping configuration Lead Lag and Low pressur...

Page 5: ...d Note that after a high level is triggered the pumps will both run until the pump Start and Stop inputs are opened Typical operation for Mode D Low pressure switch set at say 200kPa Lag pump pressure...

Page 6: ...roller press and hold the Mute Reset button on the keypad continuously for a period of 3 seconds until an acknowledgement beep is heard Pump Fault A Pump Fault is indicated for two types of Faults A T...

Page 7: ...LE PUMP 1 ISOLATOR 20amp 2 POLE PUMP 2 ISOLATOR CONTACTOR 2 PUMP 2 DATA OUTPUT 2amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 12Vdc 240Vac INPUT 1 SWITCH INPUT 2 SWITCH I...

Page 8: ...to Automatic Pumping Mode The pump is set to Manual Pumping Mode To turn pump off DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER Dual Pump Controller PUMP 1 PUMP 2 AUTO OFF AUTO OFF MAN MAN MUTE RE...

Reviews: