MAC-PLUS
11
7. Installation instructions
Installation steps:
1
Place and mount the Mac Plus
2
Connect the Mac Plus
3
Configure the Mac Plus
These three steps are described in this chapter.
WARNING!
Read the entire manual before installing the Mac Plus. Keep the manual at a safe location
for future reference.
•
Install the Mac Plus in a well-ventilated room protected against rain, snow, spray, vapour, bilge,
moisture and dust.
•
Operating temperature range: -20 up to +60 ºC, >40 ºC derating power
•
Never use the Mac Plus at a location where there is danger of gas or dust explosions.
•
Mount the Mac Plus in such a way that obstruction of the airflow through the heatsink is
prevented. No objects must be located within a distance of 10 cm / 4 inch around the Mac Plus.
•
Do not install the Mac Plus in the same compartment as the batteries. Do not mount the Mac
Plus straight above the batteries because of possible corrosive sulphur fumes.
•
Be sure that the output of the supplying source is switched off during installation. Also be sure
that no consumers are connected to the batteries during installation, to prevent hazardous
situations.
•
Use cables with an appropriate size, see the table below.
Recommended wire sizes DC input/output
Model
Minimum wire size Input
Minimum wire size Output
12/12-50
16 mm
2
16 mm
2
12/24-30
16 mm
2
10 mm
2
24/12-50
10 mm
2
16 mm
2
24/24-30
10 mm
2
10 mm
2
Min. 3 Nm – max. 5 Nm
Summary of Contents for Mac Plus 12/24-30
Page 2: ...2 MAC PLUS ...
Page 8: ...8 MAC PLUS 4 Dimensions 146 mm 198 mm 255 mm 66 mm 165 mm ...
Page 10: ...10 MAC PLUS 6 Identification label Identification label ...
Page 13: ...MAC PLUS 13 Installation drawing A Installation drawing B ...
Page 28: ...28 MAC PLUS Do not make ring networks Do not make T connections in the network ...
Page 34: ...34 MAC PLUS ...
Page 35: ...MAC PLUS 35 ...