ChargeMaster Plus 24/80-2, 24/110-2
–
User and Installation Manual
27
Malfunction
Possible cause
What to do
Charge voltage too high
Check settings (see chapter 4)
Remote panel
display shows no
ChargeMaster Plus
Display is switched off
Switch on display, refer to display manual
Error in the wiring
Check the network cables
No terminating device placed at the
ends of the network
A network needs a terminating device on
both ends of the network, check if
available
Network is configured as a ring
network
Ring networks are not allowed. Check the
connections of the network.
ChargeMaster Plus is not
configured in CZone configuration
file
Open CZone Configuration Tool and
check.
ChargeMaster Plus Dipswitch not
correct
Open CZone Configuration Tool and
check with Force Dipswitch for Address.
Slow or no
MasterBus
communication
Error in the MasterBus wiring
Check the network cables
No MasterBus Terminator placed at
the ends of the network
MasterBus needs a terminating device on
both ends of the network. Check if
connected
MasterBus network is configured
as a ring network or there are T-
connections
Ring networks and T-connections are not
allowed. Check the connections of the
network