STEP #1

Evacuate hoses used on recovery/recycle system to remove air and moisture. 

This operation must be done before 

recovery or charging of refrigerant.

1.  Connect recycle module, A/C system, DOT recovery tank, scale for use with recovery tank and recovery machine 

“figure 1”.

2.  Open “valves 1, 2, 10, 11, 15 and 16”, inlet and outlet valve on recovery machine, and valve on vacuum pump (if 

equipped). Do not open valves on DOT tank or A/C system. Turn on vacuum pump. Hoses and recovery/recycle system 
will be evacuated of air, moisture and any residual gases. When using Mastercool Recovery Machine, turn yellow 
middle knob on recovery machine to 

“purge”

 position. This will accelerate evacuation of recovery machine.

3.  When sufficient vacuum has been produced shut off “valve 1” and valve on vacuum pump (if equipped), turn off 

vacuum pump.

STEP #2

Recover refrigerant from A/C system. Use this step if refrigerant is known to be in A/C system.

1.  Connect system per “figure 1”. Evacuate system per 

STEP #1

2.  Open both high and low pressure valves on A/C system. 

3.  Open vapor “valve 6” on DOT tank. 

Note: Fill DOT recovery tank to a maximum of 80% by weight. Use scale with DOT tank to insure a maximum of 
80% full.

4.  Start recovery machine. Refrigerant (liquid and/or vapor) will flow out of A/C system high and low ports through recycle 

module, through recovery machine and into DOT tank. Recovery machine will shut off when sufficient vacuum is 
achieved in A/C system (about -10 to -14 inches of HG, -.3 to -.45 bar).

5.  Switch recovery machine to purge mode and operate until machine shuts off under vacuum conditions. Maximum 

amount of refrigerant that can be removed from system by using recovery system is now complete.

STEP #3

Create high vacuum in A/C system (prepare for refrigerant charging). 

If any refrigerant is in A/C system complete step 

#2 before starting step #3.

1.  Connect system per “figure 1”. Evacuate system per 

STEP #1

.

2.  Open high and low pressure valves on A/C system. 

3.  Turn on vacuum pump. Open “valve 1” and valve on vacuum pump (if equipped).

4.  After a high vacuum is achieved close “valve 10”. Continue running vacuum pump until very high vacuum is achieved.

5.  Close high and low pressure valves on A/C system.

6.  Close “valve 1” and vacuum pump valve (if equipped). Turn off vacuum pump.

STEP #4

Charging of A/C system with liquid refrigerant. 

Make sure system allows charging with liquid refrigerant. Check and 

make sure A/C system has been evacuated or refrigerant in A/C system is the same as charging refrigerant.  

1.  Connect system per “figure 1” if A/C system can be charged with liquid refrigerant into high side connection. If A/C 

system is to be completely charged, complete 

STEPS #1, #2 and #3

 and then continue to number 2. If system is to 

have refrigerant added to existing charge, complete 

STEP #1

 only, then continue to number 2.

2.  Dot tank should be installed on a scale to monitor the amount of refrigerant being put into A/C system. Close “valve 

10”. Open high and low side valve on A/C system. Refrigerant may or may not flow thru sight glass at this time 
depending on temperature and pressure of A/C system.

3.  Check scale weight for amount of refrigerant in DOT tank. Record weight to use later in determining amount of 

refrigerant that has gone into A/C system. Open “valve 10”. Close “manifold inlet valve 16”. Open “valves 6 and 7” on 
dot tank. Turn on recovery machine. Check scale for amount of refrigerant going from dot tank to A/C system.

4.  When proper amount of refrigerant has been added close “valve 7”, low side and high side valve on A/C system. 

Continue to run recovery machine. Recovery machine will shut off when vacuum level on inlet of recovery machine 
reaches the proper vacuum reading. Open “manifold inlet valve 16” and recovery machine will start and run until 

Summary of Contents for 69500

Page 1: ...eutsch Fran ais Espa ol English OPERATING INSTRUCTIONS RECOVERYMATE MODEL 69500 BEDIENUNGSANLEITUNG RECOVERYMATE MODEL 69500 MANUEL D OP RATION RECOVERYMATE MOD LE 69500 INSTRUCCIONES DE OPERACION REC...

Page 2: ...ontains liquid refrigerant under high pressure Never over fill recovery tank Tanks should be filled to a maximum of 80 of capacity only Use scale only to continuously monitor the recovery tank weight...

Page 3: ...f any refrigerant is in A C system complete step 2 before starting step 3 1 Connect system per figure 1 Evacuate system per STEP 1 2 Open high and low pressure valves on A C system 3 Turn on vacuum pu...

Page 4: ...oil separator will drain into container Close valve 9 Dispose of oil in an approved manner FILTER MAINTENANCE Filter should be changed on a regular basis The frequency will depend on the condition of...

Page 5: ...l ssiges K ltemittel unter hohen Druck Die K ltemittelflasche darf NIEMALS berf llt werden Die Beh lter sollten bis maximal 80 deren Inhalt gef llt sein Das Gewicht der K ltemittelflasche sollte dauer...

Page 6: ...einigungsverfahren Purge und warten bis das Ger t sich automatisch ausgeschaltet hat Vakuum erreicht Hiermit ist die Maximale K ltemittelmenge welche mit dem Absaugger t aus der KK Anlage abgesaugt we...

Page 7: ...h jedem Einsatz des Recyclingmoduls muss das l vom Abscheider abgelassen und entnommen weredn damit die Mischung von verschiedenen lsorten vermieden wird 1 Nach dem Absaug Recycle Verfahren bei einem...

Page 8: ...ression Ne jamais surcharger la bouteille de r cup ration Une bouteille devrait tre remplie au maximum 80 de sa capacit Utiliser une balance pour observer de fa on continue le poids de la bouteille Ut...

Page 9: ...cup rable avec une unit de r cup ration a t transf r MODE 3 EVACUATION DU SYSTEME Cr er un vide profond dans le syst me R AC pr paration de charge de r frig rant S il y a du r frig rant qui reste dans...

Page 10: ...t s Fermer les vannes 10 et 11 sur le s parateur d huile Placer un petit conteneur sous la vanne 9 2 Avec le s parateur d huile dans la position verticale ouvrir la vanne 9 gentiment L huile sera drai...

Page 11: ...del sistema de reciclaje 5 El tanque de recuperaci n contiene l quido refrigerante bajo alta presi n Nunca llene el tanque por encima del l mite El tanque se debe de llenar a un m ximo de el 80 de su...

Page 12: ...rado del sistema usando el sistema de recuperaci n se ha completado ahora PASO 3 Crear alto vac o en el sistema A C preparar para carga de refrigerante Si hay alg n refrigerante en el sistema A C comp...

Page 13: ...n 1 Despu s de cada operaci n de recuperaci n reciclaje cuando una baja presi n residual 5 10 PSI 3 7 bar existe en la unidad cierre las valvulas 10 y 11 2 Con el separador de aceite en posici n verti...

Page 14: ...14 www mastercool com 69500 INT INST USA 973 252 9119 Belgium 32 0 3 777 28 48 Brasil 55 11 4407 4017...

Reviews: