80
8.2 Error Code
9 Fault Diagnosis and Solutions
The inverter is easy to maintain. When you encounter the following problems, please refer to the
Solutions below, and contact the local distributor if the problem remains unsolved.
The following table lists some of the basic problems that may occur during the actual operation as well
as their corresponding basic solutions.
F00
F01
F02
F04
F05
F06
F07
F08
F09
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F20
F32
Codes
English description
Soft Time Out
INV Volt Short
GFCI Sensor Fault
Bus Volt Low
Bus Volt High
Bus Short Circuit
PV ISO Under Fault
PV Input Short Circuit
Bypass Relay Fault
INV Curr Over
INV DC Over
Ambient Over Temp
Sink Over Temp
Grid Relay Fault
DisChg Curr Over
Chg Curr Over
Current Sensor Fault
INV Abnormal
EPS Relay Fault
Alway Over Load
SCI Fault
User Manual
81
Fault diagnosis table
Soft Time Out
INV Volt Short
GFCI Sensor Fault
Bus Volt Low
Bus Volt Short
PV ISO Under Fault
PV Input Short Circuit
Relay Fault
INV Current Over
INV DC Over
F00
F01
F02
F04
F05
F06
F07
F08
F09
F14
F19
F10
F11
Types
Codes
English description
(1) Restart the inverter and wait until it functions normally;
(2) Contact customer service if error warning continues.
(1) Cut off all the power and shut down all the machines; disconnect the
load and plug in to restart machines, then check whether the load is
short circuited if the fault has been eliminated;
(2) Contact customer service if fault remains unremoved.
(1) Cut off all the power, Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning continues.
(1) Check the input mode setting is correct.
(2) Restart the inverter and wait until it functions normally.
(3) Contact customer service if error warning continues.
(1) Restart the inverter and wait until it functions normally.
(2) Contact customer service if error warning continues.
(1) Check for good ground connection;
(2) Check if the earth resistance of PV+ and PV- is greater than 2MΩ;
(3) If it is smaller than 2MΩ, check PV string for ground fault or poor
ground insulation; if it is greater than 2MΩ, please contact the local
inverter customer service once fault is not removed.
(1) Check the input mode setting is correct.
(2) Disconnect the PV input, restart the inverter and wait until it
functions normally.
(3) Contact customer service if error warning continues.
(1) Disconnect the PV input, restart the inverter and wait until it
functions normally.
(2) Contact customer service if error warning continues.
(1) Wait five minutes for the inverter to automatically restart;
(2) Check whether the load is in compliance with the specification;
(3) Contact customer service if error warning continues.
(1) Restart the inverter and wait until it functions normally.
(2) Contact customer service if error warning continues.