66
•
Threshold setting value: The value set by upper
computer software.
•
Threshold setting trip time: The trip time set by upper
computer software.
•
Threshold auto test value: The value of threshold
during coincidence between the threshold and
current measured value.
•
Threshold auto test trip time: The time from the
coincidence between the threshold and current to
the trip signal of disconnection switch. Current
measured voltage or frequency value: The
measurement value of grid voltage or frequency
during the coincidence.
Interface
Description
FACMAX (S1)
Set:
50.2Hz 100ms
Tes:
50.2Hz 94ms
Cur:
49.9Hz Pass!
FACMAX (S2)
Set:
51.5Hz 100ms
Tes:
51.5Hz 94ms
Cur:
49.9Hz Pass!
•
Threshold setting value: The value set by upper
computer software.
•
Threshold setting trip time: The trip time set by
upper computer software.
•
Threshold auto test value: The value of threshold
during coincidence between the threshold and
current measured value.
•
Threshold auto test trip time: The time from the
coincidence between the threshold and current to
the trip signal of disconnection switch.
•
Current measured voltage or frequency value: The
measurement value of grid voltage or frequency
during the coincidence.
Interface
Description
FACMIN (S1)
Set:
49.8Hz 100ms
Tes:
49.8Hz 97ms
Cur:
49.9Hz Pass!
FACMIN (S2)
Set:
47.5Hz 100ms
Tes:
47.5Hz 94ms
Cur:
49.9Hz Pass!
User Manual
67
4.4 Inquiry
❶
Machine model
❷
Serial number
❸
Firmware Version
❹
Running records
Press UP/DOWN button to move corresponding options;
Press Enter button to jump to the selected menu.
Press ESC button to return to user interface.
There are four alternative options: machine model, serial
number, firmware version and running records (refer to 1
to 5).
Interface
Description
-INQUIRE-
1: INV MODULE
2: MODULE SN
3: FIRMWARE
4: RECORD
5: BMS INFO
This interface displays machine model of the inverter.
Press ESC button to return to inquiry interface.
Interface
Description
-INVERTER-
GreenE 3.68K-5K
This interface displays serial number of the inverter.
.Press ESC button to return to inquiry interface.
Interface
Description
-SERIAL NUMBER-
SN:
123456789532625
This interface displays firmware version for ARM and DSP
of the inverter.
.Press ESC button to return to inquiry interface.
Interface
Description
-FIRMWARE-
ARM VER:
1.0.0
DSP VER:
1.0.0
SN of the fault: Fault warning codes (500 at utmost) (the
latest fault or alarm marked as No.1) Time of the fault:
Press UP/DOWN button to view the record. Press ENTER
button to enter the description interface for corresponding
records. Press ESC button to return to Inquiry interface.
Interface
Description
-REC (170)-
1:
F10-1
DATE:
2018 - 12-01
TIME:
00
:
01
:
02