User Manual
P a g e
|
75
of
100
Procedure for calibration of ET Source Mode
To enter into the ET Source Calibration, Select the
ET
option and
press
F1
key. To calibrate the ET mode first select the Output Type
which to be calibrated.
Or
Expected Values of Zero and Span for source calibration are as per
below table.
Input Type
Group
Recommended
Calibration Points
mA
(0.000 to 24.000
mA)
1. 0.000 to 12.000 mA
ZERO: 1.000 mA
SPAN: 10.000 mA
2. 12.000 to 24.000 mA
ZERO: 12.000 mA
SPAN: 22.000 mA
V
(0.000 to 12.000
V)
1. 0.000 to 6.000 V
ZERO: 1.000 V
SPAN: 4.000 V
2. 6.000 to 12.000 V
ZERO: 6.000V
SPAN: 11.000V