Model: LC5296-AT /LC5248E-AT/LC5296V-AT
masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual
Page 21 of 44
6.3 RUN Time Indication/Function
Following parameters can view or change during run time.
Press Decrement key to show percentage power Auto Mode (0.0 to 100.0%)
For Thermocouple input type, Press Increment key to show ambient
temperature.
During manual mode, Increment key and Decrement Key will use to
modify the percentage power.
Press
to toggle between AUTO & MANUAL mode or display time.
6.4 Set Point Setting
*Last
decimal point of PV display “ON”, indicates RUN.
6.5 AUTO TUNE MODE
6 . 4 S e t P o i n t S e t t i n g
Set Point Setting:
Parameter
(PV display)
Setting name and
description
Default
value
Shows
only if
Symbol
Name
C1.SP
(
C1.sp
)
Control Set Point 1
Range Depending on PV
sensor type selected
100
-
A1.SP
(
A1.sp
)
Alarm Set Point 1
Range Depending on PV
sensor type selected
100
Output Type is
LIN(Linear)
A2.SP
(
A2.sp
)
Alarm Set Point 2
Range Depending on PV
sensor type selected
100
-
SOKT*
(
sok.t
)
Soak Run/stop
To Run/Stop Soak time
stop
Soak rate
(
sok.r
) is
not 0
AUTOTUNE PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if Only
Symbol
Name
A.TUN
(
A.tun
)
Auto Tune
Start / Stop Auto Tuning Process
yes
/
no
0 : NO (Stop Auto Tuning)
1 : YES (Start Auto Tuning)
NO
Control Type(COP)
is PI or PID
PB
(
pb
)
Proportional
Band
Adjust Proportional Band
0 to 9999 or 0.0 to 999.9
1 0 .0
Control Type(COP)
is P or PI or PID
TI
(
ti
)
Integral Time
Adjust Integral Time
0 to 1000
6 0
Control Type(COP)
is PI or PID
TD
(
td
)
Derivative Time
Adjust Derivative Time
0 to 180
0
Control Type(COP)
is PID