Model: LC5296-AT /LC5248E-AT/LC5296V-AT
masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual
Page 25 of 44
* R.D-2
(
r.d-2
)
Retransmission-2
Direction
Set Direction for the Retransmission Output-2
rev
/
dir
0 : REV (REVERSE)
1 : DIR (DIRECT)
1
(DIRECT)
OT
(
ot
)
Output Type
Output Type
rely
/
ssr
/
lin
0 : RELY (Relay)
1 : SSR (Voltage Pulse Output)
2 : LIN (Linear)
3 : VPFN (Motor position control without slide wire
feedback)
Device can support RELAY or SSR output once at a
time. (Factory Settable)
** Device can support Control output type
PID
or
onoF.
(Factory Settable)
0
(Relay)
**VPFN, LIN and
SSR option will not
appear if
COP(Control Type)
is ON-OFF
COP
(
Cop
)
Control Output
Type
Select Controlling Type for Output
P
/
Pi
/
pid
0 : P (Proportional Control)
1 : PI
2 : PID
0
(P Type)
Control output
type is PID
CO.LO
(
Co.Lo
)
Control Output
Low Limit in %
Control Output Low Limit in %.
0.0 to 100.0 %
(It will be always less then CO.HI)
0 .0
Control output
type is PID
CO.HI
(
Co.Hi
)
Control Output
High Limit in %
Control Output High Limit in %.
0.0 to 100.0 %
(It will be always greater then CO.LO)
1 0 0 .0
Control output
type is PID
A1TP
(
a1tp
)
Alarm Type
–
1
Refer ALARM Type Table on Page.39
0 to 15
6
(PV.A.L.)
Output Type is
LIN(Linear)
A2TP
(
a2tp
)
Alarm Type
–
2
Refer ALARM Type Table on Page.39
0 to 15
6
( PV.A.L.))
Output Type is not
VPFN
A1HY
(
a1HY
)
Alarm 1 Hysteresis
Set Hysteresis(in °C) for Alarm-1
1 to 100
TC & RTD Input
0.1 to 100.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 100.0
Linear Input with DP=1
0.01 to 10.00
Linear Input with DP=2
0.001 to 1.000
Linear Input with DP=3
1
Output Type is
LIN(Linear)
A2HY
(
a2Hy
)
Alarm 2 Hysteresis
Set Hysteresis(in °C) for Alarm-2
1 to 100
TC & RTD Input
0.1 to 100.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 100.0
Linear Input with DP=1
0.01 to 10.00
Linear Input with DP=2
0.001 to 1.000
Linear Input with DP=3
1
Output Type is not
VPFN
A1LC
(
a1lC
)
Alarm 1 Logic
Set Logic for Alarm-1
norm
/
flsf
0 : NORM (Normal)
1 : FLSF (Fail-Safe)
Page. 37 shows operation diagram of different alarm Type for
Alarm Logic NORM (Normal). For Fail-Safe Logic Alarm will
work completely opposite to Normal behavior. (i.e. for any
particular condition when Relay is ON for Normal logic, for
that condition relay will OFF for Fail-Safe Logic & vice-versa)
0
(Normal)
Output Type is
LIN(Linear)