Temperature Indicator: 409-4IN
REF NO: m47/om/201
Issue NO: 04
Page 26 of 34
10.
Span display
40002
Integer
R/W
11.
Set point 1
40003
Integer
R/W
12.
Set point 2
40004
Integer
R/W
13.
Relay delay
40005
Unsigned Integer
0
9999
R/W
14.
Brightness
40006
Unsigned char
1
100
R/W
15.
*Input type selected
40007
Unsigned Integer
0
18
R/W
16.
*Decimal point
40008
Unsigned char
0
4
R/W
17.
Hysteresis
40009
Integer
0
255
R/W
18.
Serial number
40010
Unsigned Char
1
247
R/W
19.
*Baud rate
40011
Unsigned char
0
3
R/W
20.
*Alarm logic type
40012
Unsigned Integer
0
2
R/W
21.
*Alarm 1
40013
Unsigned Integer
0
1
R/W
22.
*Alarm 2
40014
Unsigned Integer
0
1
R/W
23.
*Alarm Latch
40015
Unsigned Integer
0
1
R/W
24.
* Alarm sensor
40016
Unsigned char
0
1
R/W
25.
*Relay control
40017
Unsigned Integer
0
1
R/W
26.
Password
40018
Unsigned integer
1
9999
R/W
27.
Serial Input PV
40031
Integer
-1999
9999
R/W
28.
Time out
40032
Unsigned Integer
1
32
R/W
29.
*Sqrt
40033
Unsigned char
0
1
R/W
30.
*Filter
40034
Unsigned integer
0
60
R/W
31.
*Retransmission o/p
40035
Unsigned char
0
4
R/W
32.
Inlo
40036
Integer
0
15
R/W
33.
Inhi
40037
Integer
0
15
R/W
Table 12.
*Relay status1, *Relay status2 it gives status of LED. Relay status1 can be used to
acknowledge
Alarm 1 Blinking, Alarm 2 Blinking : 1= Blinking On, 0 = Blinking Off
Acknowledge using function code-5
Address 3-16 for future use only