Page 10 of 34
RUN Time Indication/Function
Following parameters can view or change during run time.
For Thermocouple input type, Press Decrement key to show ambient temperature.
For Alarm Acknowledgment, Press Enter Key.
Set Point Setting
Configuration Mode
Parameter
(PV display)
Setting name and
description
Default
value
Shows only if
Symbol
Name
ST-1
(
st-1
)
Set Point 1
Range Depending on PV sensor type
selected
100
-
ST-2
(
st-2
)
Set Point 2
Range Depending on PV sensor type
selected
100
-
CONFIGURATION PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if Only
Symbol
Name
INPT
(
inpt
)
INPUT Type
Set PV Input Type
tC e
/
tC j
/
tC K
/
tC t
/
tC b
/
tC r
/
tC
s
/
rtd.1
/
0-.4K
/
0-6K
/
1-10
/
0-10
/
0-5v
/
1-
5v
/
0-2V
/
.4-2
/
1020
/
1-75
/
0-
75
/
serl
/
4-20
/
0-20
/
Value
Input Type
Range
0
TC E
-200 to 1000 °C
1
TC J
-200 to 1200 °C
2
TC K
-200 to 1372 °C
3
TC T
-200 to 400 °C
4
TC B
450 to 1800 °C
5
TC R
0 to 1768 °C
6
TC S
0 to 1768 °C
7
RTD.1
-199.9 to 850.0 °C
8
0-.4K
-1999 to 9999
9
0-6K
10
+10V
11
0-10 V0
12
0-5 V
13
1-5 V
1 -5 V