Temperature Indicator : 409-4IN

 

REF NO: m47/om/201 

 

 

Issue NO: 04

 

Page 17 of 34 

 

Process value greater then maximum value of zero/span then display will show OPEN 
message. Retransmission o/p will follow 5% of display range and then it will give fixed 
o/p depending up on OPEN sensor selection. In case of linear inputs scaling is applied 
then during OPEN sensor condition it may not show OPEN message instead it will 
show either OVER/UNDER. 

Retransmission output during OPEN sensor/Diode Open condition 

 

I/P 

0-20 mA O/P 

4-20 mA O/P 

 

UP Scale O/P 

DW Scale O/P 

UP Scale O/P  DW Scale O/P 

*TC 

21.00 

0.0 

20.8 

3.2 

Pt-100 

21.00 

0.0 

20.8 

3.2 

0~5V 

21.00 

0.0  

3.2 

3.2 

1~5V 

21.00 

0.0 

20.8 

3.2 

±75mV 

21.00 

0.0 

20.8 

3.2 

0~75mV 

21.00 

0.0 

20.8 

3.2 

0~10V 

Random 

Random 

Random 

Random 

*±10V 

Random 

Random 

Random 

Random 

0~2V 

21.00 

0.0 

20.8 

3.2 

0.4~2V 

21.00 

0.0 

20.8 

3.2 

-10~20mV 

21.00 

0.0 

20.8 

3.2 

0~6000Ω 

21.00 

0.0 

20.8 

3.2 

0~400Ω 

21.00 

0.0 

20.8 

3.2 

Serial 

21.00 

0.0 

20.8 

3.2 

4-20mA 

21.00 

0.0 

20.8 

3.2 

0-20mA 

21.00 

0.0 

3.2 

3.2 

 

Table 5A 

 

 

 

Summary of Contents for 409-4IN

Page 1: ...ge 1 of 34 User s Manual 409 4IN Temperature Indicator Masibus Automation and Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India Phone 91 79 23287275 79 Fa...

Page 2: ...Configuration Mode 10 Calibration Mode 13 6 CONTROL FUNCTION 15 6 1 ON OFF Control 15 6 2 Messages during OPEN SENSOR condition 16 Retransmission output during OPEN sensor Diode Open condition 17 6 3...

Page 3: ...nsumption 30 Insulation resistance 30 Environment 30 Case 30 Mounting method 31 Dimension 31 Panel Cutout 31 Weight 31 Communication 31 Transmitter Output 31 Isolation specification 31 Special Feature...

Page 4: ...facilitates plant operator to use in any application 409 4IN is easy to operate and configuration is user friendly Model and Suffix code Check the model and suffix codes to confirm that the product r...

Page 5: ...e harm to users and damage to the property and to use the product safely Understand the following description signs and symbols read the text and Observe Descriptions DESCRIPTION OF SIGNS 3 Front Pane...

Page 6: ...save the parameters to nonvolatile memory when user setting a proper data by Increment and decrement key for parameter configuration PV Present Value Display PV 4 digital 4 inch RED Display Display pr...

Page 7: ...unt Fig 4 Terminal Arrangement for Wall mount 4 1 Terminal Description Terminal Description SYMBOL L Mains Supply 90 270VAC N E NC1 Normally close 1 Relay 1 NO1 Normally open 1 C1 Common 1 NC2 Normall...

Page 8: ...Temperature Indicator 409 4IN REF NO m47 om 201 Issue NO 04 Page 8 of 34 Table 3 RTD common For RTD Input Only Three wire Compensation D Rs 485 Communication Serial Input D Rx Retransmission Output Rx...

Page 9: ...Temperature Indicator 409 4IN REF NO m47 om 201 Issue NO 04 Page 9 of 34 5 Menu Layout Menu Layout...

Page 10: ...e Depending on PV sensor type selected 100 ST 2 st 2 Set Point 2 Range Depending on PV sensor type selected 100 CONFIGURATION PARAMETERS Parameter PV display Setting Name Description Default Value Sho...

Page 11: ...Lower Range with changing of Input Type Refer Above Table Can be set to any value within the Input Range less the SPAN Value 1 000 if 1 5V Only in Linear input INHI inhi In High Range Automatically c...

Page 12: ...t with DP 3 0 1 LACH LACH Latch Enable or Disable Latch yes no 0 YES 1 NO 1 NO CTRl CTRL Control Relay Select Control Relay Status on off 0 ON 1 OFF 0 OFF SRNO srno Serial No Unit ID for Modbus RS485...

Page 13: ...Default Value Show if Only Symbol Name AMB Amb Ambient Ambient Adjustment Input is TC CALZ Calz Calibration Zero Calibration Zero for PV Input PV Display Current PV CALS Cals Calibration Span Calibrat...

Page 14: ...Temperature Indicator 409 4IN REF NO m47 om 201 Issue NO 04 Page 14 of 34 Example 1 How to change Input Type 2 How to change Control Set Point 1...

Page 15: ...below In cases where this cycling occurs rapidly and to prevent contactors and valves from getting damaged an on off differential or hysteresis is added to the controller operations On Off hysteresis...

Page 16: ...ill display readings above 5 of display range then after it will show OVER UNDER message until value crosses maximum value of Sensor range Input type Message TC E OPEN TC J OPEN TC K OPEN TC T OPEN TC...

Page 17: ...it will show either OVER UNDER Retransmission output during OPEN sensor Diode Open condition I P 0 20 mA O P 4 20 mA O P UP Scale O P DW Scale O P UP Scale O P DW Scale O P TC 21 00 0 0 20 8 3 2 Pt 1...

Page 18: ...dom 0 2V 10 50 0 0 5 25 0 0 5 20 0 80 0 4 2V 10 50 0 0 5 25 0 0 5 20 0 80 10 20mV 10 50 0 0 5 25 0 0 5 20 0 80 0 6000 10 50 0 0 5 25 0 0 5 20 0 80 0 400 10 50 0 0 5 25 0 0 5 20 0 80 Serial 10 50 0 0 5...

Page 19: ...CK Normal ACK High Alarm Latch Yes LAMP OFF FLASH FLASH OFF FLASH OFF RELAY OFF ON ON OFF OFF OFF Alarm Latch No LAMP OFF FLASH FLASH OFF OFF OFF RELAY OFF ON ON OFF OFF OFF Trip LAMP OFF FLASH OFF OF...

Page 20: ...ON OFF High Alarm Latch Yes LAMP OFF FLASH FLASH OFF FLASH OFF RELAY OFF ON ON OFF OFF OFF Alarm Latch No LAMP OFF FLASH FLASH OFF OFF OFF RELAY OFF ON ON OFF OFF OFF Trip LAMP OFF FLASH OFF OFF FLASH...

Page 21: ...ON ON OFF OFF Alarm Latch No LAMP OFF FLASH OFF FLASH STEADY OFF OFF RELAY OFF ON OFF ON OFF OFF OFF Trip LAMP OFF FLASH OFF OFF STEADY STEADY OFF RELAY OFF ON OFF OFF ON ON OFF VLOW Alarm Latch Yes...

Page 22: ...No LAMP OFF FLASH FLASH OFF STEADY OFF OFF RELAY OFF ON ON OFF OFF OFF OFF Trip LAMP OFF FLASH OFF OFF STEADY STEADY OFF RELAY OFF ON OFF OFF ON ON OFF High Alarm Latch Yes LAMP OFF FLASH FLASH OFF S...

Page 23: ...r CALZ or CALS because for other inputs except thermocouple ambient calibration is not required 5 To perform zero calibration press DOWN key when display shows CALZ Feed input corresponding to zero an...

Page 24: ...e current output 4 To perform zero calibration press DOWN key when display shows RETZ Retransmission output will be nearly equal to 0 V 0mA depending up on type of selection If output differs from 0V...

Page 25: ...ers Use to read programmable registers 05 Force single coil Use to ON OFF single coil 16 Preset Multiple register Use to write programmable register Table 11 The error checking field contains a 16 bit...

Page 26: ...nsigned Integer 0 1 R W 22 Alarm 2 40014 Unsigned Integer 0 1 R W 23 Alarm Latch 40015 Unsigned Integer 0 1 R W 24 Alarm sensor 40016 Unsigned char 0 1 R W 25 Relay control 40017 Unsigned Integer 0 1...

Page 27: ...0 0 1 0 2 00 3 000 4 0000 Sqrt 0 YES 1 NO Filt 0 No Filter 1 60 Filter used Retransmission o p 0 0 5V 1 1 5V 2 0 10V 3 4 20mA 4 0 20mA 8 1 2 Parameter Address Details For Mtyp b 405 4IN Sr No Analog P...

Page 28: ...for the salve 06 When Master device write some parameters to Slave device If slave device busy then it will send 06 code to indicate slave device is busy Table 14 9 Technical Specifications Display PV...

Page 29: ...current and voltage input scaling is possible and decimal point can be changed Burn out current 0 25 uA Reference Junction compensation error 2 C Noise Rejection Ratio Common mode 120 dB 50Hz Normal...

Page 30: ...nce for current O P 500 or less Load Resistance for Voltage O P 3 K or more Supply voltage Standard 85 265VAC 100 300VDC Optional 18 36VDC Power consumption 10 VA Data backup Non volatile memory can b...

Page 31: ...n method Half duplex communication start stop synchronous Communication Speed 4800 9600 19200 38400bps selectable by key Parity None Communication Protocol Modbus RTU Connectable number of unit Max 32...

Page 32: ...C for 1 minute Primary terminals indicate power terminals and relay output terminals Secondary terminals indicate analog I O signal and Communication O P Insulation resistance 20M or more at 500 V DC...

Page 33: ...Temperature Indicator 409 4IN REF NO m47 om 201 Issue NO 04 Page 33 of 34 10 Appendix Troubleshooting Jumper Location for Retransmission Output Jumper Setting for Retransmission card m61Cao102...

Page 34: ...of input Vhigh is the high end of input signal range 5V or 20mA Vlow is the high end of input signal range 1V or 4mA Example PV is 0 1000 Input signal range is 1 5V Input signal is 3V PV will be PV 0...

Reviews: