Temperature Indicator : 409-4IN
REF NO: m47/om/201
Issue NO: 04
Page 11 of 34
14
0-2V
15
.4-2V
16
-10-20 mV
17
1-75 mV
18
0-75 mV
22
SERL
23
4-20 mA*
24
0-20 mA*
*
Use external 250ohms,0.1% for current input
DP
(
dp
)
Decimal Point
Set position of Decimal Point on Display.
1
/
0.1
/
0.01
/
0.001
0 : 1
1 : 0.1
2 : 0.01
3 : 0.001
1
(0 .1 )
Input Type is
Linear
ZERO
(
zero
)
Zero
Automatically change to the Input Lower Range with
changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range &
less the SPAN Value.
-199.9
(If 1-5V)
SPAN
(
span
)
Span
Automatically change to the Input Higher Range
with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range &
greater the ZERO Value.
999.9
(If 1-5V)
INLO
(
inlo
)
In Low Range
Automatically change to the Input Lower Range with
changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range &
less the SPAN Value.
1 .0 0 0
(if 1 -5 V)
Only in Linear
input
INHI
(
inhi
)
In High Range
Automatically change to the Input Higher Range
with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range &
greater the ZERO Value.
5 .0 0 0
(if 1 -5 V)
Only in Linear
input
SQRT
(
sqrt
)
Square Root
Enable or Disable Square Root
yes
/
no
0 : YES
1 : NO
0
(NO )
Only in Linear
input
FLTR
(
fltr
)
Filter
Filter is time (in sec), that PV will wait before
getting to its value after filter set.
0-60 sec
0
OPES
(
opes
)
OPEN Sensor
Status
Set Control O/P & Retransmission state when Input
OPEN condition.
up
/
down
0 : UP
1 : DOWN
0
(UP )
TA-1
(
TA-1
)
Type of Alarm
Set which Set Point to shown in SV display in RUN
mode while device is in Auto Mode
Alrm
/
Trip
0 : ALRM
1 : TRIP
0
(ALR M )
TA-2
(
TA-2
)
Type of Alarm
Set which Set Point to shown in SV display in RUN
mode while device is in Auto Mode
0
(ALR M )