User Manual
18
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
Start & Stop function:(In Run Mode)
START key
:
If this key pressed batching relays (WP/EP) gets ON & BATCH TOTAL = 0.It
means a new batch is started. If START key is pressed again and again, it
will not start the batch until WP/EP relays gets OFF.
Relays get OFF by two ways:
1. STOP key
2.
BATCH TOTAL crosses the value of SETPOINT.
STOP
key
:
If user presses
STOP
key in running batch, batching relays (WP/EP) gets off.
If again
STOP
key is pressed again and again only batching relays gets
ON/OFF (only if BATCH TOTAL < (WP/EP) values. No new batch will be
started by
STOP
key.
When batch total value crosses the WP/EP value, relays gets OFF and batch
is over.
Again if START key is pressed then a new batch will start making BATCH
TOTAL = 0. Batching relays gets ON.
8.4 Edit Mode
In this mode user can verify or modify, various parameters.
To enter the EDIT mode, correct password is to be entered.
Password Protection
When INDEX key is pressed, following prompt will be displayed at lower panel 7-segment
display.
“bAt tot” , then
“Int tot” , then
“roL Cnt “ , then
“PASSUord” .
User Can select the Parameter
–any of the above prompt to display corresponding value
by pressing INDEX key and then pressing
“START KEY”(It is digit select key for editing
the parameters),
At the selection of password,
value “0000” is displayed.
Enter the correct password value with the help of START (digit select key) and STOP key
(Incr key) and press INDEX KEY (INDEX key is used as ENTER key)
If correct password is entered & INDEX key is pressed, it will show the first mode PROG
MOD. If wrong password is entered, then “0000” MSG will be displayed again at lower
display window.
Parameter Description
There are total three Menu Items:
Three parameters are displayed after entering correct password.
These parameters related with totaliser are mentioned in the following table.
1.
Program Mode
2.
Configuration Mode
3.
Calibration Mode