User Manual
16
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
8. OPERATING DETAILS
The following paragraphs give detailed description of how to operate the unit.
Before using the instrument, make sure to study and understand this section.
8.1 Display Section:
The unit has two windows/groups of display:
Upper:
Five digits 7-
segment, 0.56” Red LED display:
It displays Flow rate/Process variable.
Lower:
Eight digits 7-
segment 0.40” Red LED display:
In normal mode of operation, Batch total/Integration Total is displayed. While in EDIT
mode, parameters are displayed in this window.
8.2 Keyboard Section
Unit has 4 key membrane keypad organized as 4 x 1 matrix.
Following Table explain the Operation of the Keys used for configuration.
SET OR INDEX
1.It will allow user to enter in EDIT mode, when instrument is in
RUN mode.
2. It will scroll menu and submenu when it is enabled
3. It will save edited data.
START OR
SHIFT
1. It will enter into the submenu, when main menu is enabled
and shows submenu‟s value.
2. It will select the digit to modify, when value is edited.
3. It will start batch, if pressed, when IT & BT are being
displayed
STOP OR
INCREMENT
1. It will increment value of digit selected or constant selected.
2. It will stop batch, if pressed, when BT/IT are being displayed.
3. For Pause batch press stop key for 1 second.
4. If we press stop key for 3 second then batch becomes zero.
ESCAPE
1. It will escape to previous status, with reference to its current
status.
Sequence of status:
IT MENU SUB-MENU
Parameter‟s Value
Escape sequence
When Esc key is pressed in Menu, the instrument will come in
RUN Mode. If user wants to go in EDIT mode, he will have to
enter the correct password again.
2. When Esc key is pressed in RUN Mode, it will directly enter
in to the set point menu. This function is only applicable when
type of instrument is totaliser.
8.3 Run Mode
Whenever mains is switched on to the unit,
Engineering value proportional to the input signal will be displayed as Process variable.
Decimal point is displayed at selected position.
Last saved batch total/integration total will be displayed on the lower window.