background image

User Manual

  

21 

Flow Indicator Totaliser 1006H

 

REF NO:m16Aom101           

 

Issue No: 03 

 

 
 

8.4.1 Program mode 

Programming menu provides facility to configure the relay for different function. 
 

 
8.4.1.1 Program Mode parameters Details 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Low alarm and high alarm: 

Value  of  Low  alarm  should  be  lower  than  that  of  high  alarm.  If  user  tries  to set value  of 
Low  alarm 

greater

  than  high  alarm  Value,  error  message  will  be  displayed.  Similarly,  if 

user  set  value  of  High  alarm 

lower

  than  low  alarm  Value,  error  message  will  be 

displayed. Alarms value cannot be set greater than Full-scale Value (FS).  
 

 

Comparison with Zero and full-scale

:  

Low Alarm value should be greater than Zero value. If user tries to set value of Low alarm 
less than Zero Value, error message will be displayed. 

If (Low Alarm< Zero valu

e), “error” message appears. 

 
High-Alarm value should be greater than Full-scale value. . If user tries to set value of 
High-alarm greater than Full-scale value, error message will be displayed. 

If (High Alarm > full-

scale value), “error” message appears. 

 

 

Set point and pre-warn: 

Error message will be displayed if, set point value is lower than pre-warn and vice versa. 
 

 

Alarm ON-OFF :  

Using these settings, user can set alarm/relay availability. If particular relay is set as  
„yes‟, that particular alarm indication will be present over the display card and relay action 
will come into effect. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

No. 

Name 

Description 

No of 

digit 

Lo 

limit 

Hi limit 

Low Alarm 

Alarm 

conditions for 

flow rate. 

999998 

High Alarm 

999999 

Pre warn 
Alarm 

Batch control 

values. 

999998

 

Set Point 
Alarm 

999999

 

rEL1 
(Relay 1) 

Low alarm /Pre-warn/no 

rEL2 
(Relay 2) 

High alarm /Set Pnt /no 
 

Filter no 

 

25 

Summary of Contents for 1006H

Page 1: ...DICATOR TOTALISER 1006H Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79 23287281 82 Email support masibus com...

Page 2: ...ification 9 3 12 Communication 10 3 13 Other Specification 10 3 14 Physical Specification 10 4 FRONT AND REAR PANEL DESCRIPTION 11 4 1 Front Panel Description 11 4 2 Rear Panel Diagram 11 5 MECHANICAL...

Page 3: ...9 1 Input Calibration 29 9 2 Output Calibration 29 9 2 1 out zero and out span 29 10 COMMUNICATION GUIDELINES 30 10 1 Introduction 30 10 2 Function Code for Modbus 30 10 3 Modbus RTU protocol address...

Page 4: ...nu driven with user understandable prompts For protecting programmed data password protection facility is provided Integrated total batch total and roll count are cleared by special password The produ...

Page 5: ...nts before using the product If the product is different from that which you have ordered if any parts or accessories are missing or if the product appears to be damaged contact your sales representat...

Page 6: ...rify the ratings of the output devices and the inputs are as specified o Provide Power from a single phase instrument power supply If there is a lot of noise in the power line insert an insulating tra...

Page 7: ...lowable signal source Resistance 0 031 100 or less ALLOWABLE INPUT VOLTAGE DC voltage 20V DC NOISE REJECTION RATIO Common Mode 100db Normal mode 40db RESPONSE TIME Input to relay o p 1 second Input to...

Page 8: ...AGE Flow alarm Batch relay NUMBER OF RELAY CONTACT OUTPUTS 2 Flow alarm relays Batch relays RELAY CONTACT RATING 250VAC 5Amps RELAY CONTACT TERMINAL 2 Common NO 3 6 Display Unit Specification PROCESS...

Page 9: ...ATION TERMINAL Isolated from other input output terminals and internal circuit POWER SUPPLY TERMINAL Isolated from other input output terminals and internal circuit GROUND TERMINAL Isolated from other...

Page 10: ...600 19200 bps MAX CONNECTABLE CONTROLLERS INDICATOR 32 ADDRESS RANGE 1 to 99 3 13 Other Specification SQUARE ROOT EXTRACTION Applicable DIGITAL FILTER Applicable TIME BASE UNIT Second minute hour day...

Page 11: ...1 User Manual 11 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 4 FRONT AND REAR PANEL DESCRIPTION 4 1 Front Panel Description 4 2 Rear Panel Diagram...

Page 12: ...ument with the panel using two side brackets All the electrical connections to be done at back panel on screw type terminals Make sure that no wire is connected loosely to avoid generation of spark an...

Page 13: ...1 User Manual 13 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 6 TERMINAL CONNECTION DETAILS...

Page 14: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 14 7 WIRING DIAGRAM 7 1 Wiring Diagram of 1006H...

Page 15: ...dicator Totaliser 1006H REF NO m16Aom101 Issue No 03 7 2 Wiring Diagram and Jumper Setting of Pulse Input 7 2 1 NPN Proximity Input Jumper Setting 7 2 1 A NPN Proximity Input 7 2 1 B Dry Contact With...

Page 16: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 16 7 2 2 PNP Proximity Input Jumper Setting 7 2 2 A PNP Proximity Input 7 2 2 B Dry Contact With PNP Input Jumper Setting...

Page 17: ...1 User Manual 17 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 7 2 2 C Wet Contact 10Vdc With PNP Input Jumper Setting 7 2 2 D Wet Contact 10Vdc With PNP Input Jumper Setting...

Page 18: ...OR SHIFT 1 It will enter into the submenu when main menu is enabled and shows submenu s value 2 It will select the digit to modify when value is edited 3 It will start batch if pressed when IT BT are...

Page 19: ...tal is updated continuously proportional to input Rollover Count RC This is a two digit value displayed as the rollover that takes place when integrated total gets higher than higher limit When the in...

Page 20: ...roL Cnt then PASS User Can select the Parameter any of the above prompt to display corresponding value by pressing INDEX key and then pressing START KEY It is digit select key for editing the paramete...

Page 21: ...or message will be displayed If Low Alarm Zero value error message appears High Alarm value should be greater than Full scale value If user tries to set value of High alarm greater than Full scale val...

Page 22: ...ff 4 000 0 999 9 14 DP Decimal Point 0 0 1 0 01 0 001 15 SF1 Full Scale For Segment 1 6 000000 999999 16 FL1 Age Of Full Scale Segment 1 10 20 30 40 50 60 70 80 90 100 17 SF2 Full Scale For Segment 2...

Page 23: ...l work One digital input is there For Start Stop Function DIG I P 24VDC DIG I P GND When any of these inputs is connected to DIN it will perform its specific function Digital Filter If Digital filter...

Page 24: ...ive different segments of the full scale input in percentage with Full scale engineering value for each segment We have to program the value of flow rate at different inputs Here we are defining five...

Page 25: ...ters minute conversion factor is 1 then it will simply integrate process value as it is If we change conversion factor 2 then it will divide process value by that factor i e 100 2 50 it integrates tha...

Page 26: ...ormula for linear mode For any type of input Indication Engineering Value X Zero CALS CALZ X Input signal CALZ Full scale Zero CALZ Value of input applied during zero calibration CALS Value of input a...

Page 27: ...1 User Manual 27 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 8 5 Parameter Flow How to operate menu is shown below in the form of flow diagram...

Page 28: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 28...

Page 29: ...ill be stored as Span Now the instrument is calibrated 12 Press ESC key to come out from SPAn1 9 2 Output Calibration For output calibration measuring instrument should be at least 3 times accurate 9...

Page 30: ...ding registers Use to read PV Control RSP output etc 05 Write input registers Use to write digital parameter value 06 Preset Single register Use to write programmable register The error checking field...

Page 31: ...0mA 3 for 4 20mA 4 for pulse 13 40013 Type of Inst 2 1 R W 0 for indicator 1 for Totaliser 2 for counter 14 40014 Sqrt mode 2 1 R W 0 for Yes 1 for No 15 40015 Digital input 2 1 R W 0 for Yes 1 for No...

Page 32: ...000 4094 47 40047 Out span 2 1 R W 0000 4095 48 40048 Default out 2 1 R W 0 for yes 1 for no 49 40049 Int total 2 1 Read only 50 40050 Int total 2 2 1 Read only 51 40051 Batch total 2 1 Read only 52 4...

Page 33: ...DISPLAY RX O P mA LINEAR SQUARE ROOT LINEAR SQUARE ROOT I P 1 60 OPEN OPEN 4 00 4 00 1 60 I P 3 20 UNDER UNDER 4 00 4 00 3 20 I P 4 00 Flow Rate Flow Rate 4 00 4 00 20 00 I P 20 80 Flow Rate Flow Rat...

Page 34: ...er s power follow the measures in the procedure below If a problem appears complicated contact our sales representative Masibus Automation Instrumentation Pvt Ltd Customer Support Division B 30 GIDC E...

Reviews: