8.4.1 Program mode
Programming menu provides facility to configure the relay for different function.
8.4.1.1 Program Mode parameters Details
Low alarm and high alarm:
Value of Low alarm should be lower than that of high alarm. If user tries to set value of
Low alarm
greater
than high alarm Value, error message will be displayed. Similarly, if
user set value of High alarm
lower
than low alarm Value, error message will be
displayed. Alarms value cannot be set greater than Full-scale Value (FS).
Comparison with Zero and full-scale
:
Low Alarm value should be greater than Zero value. If user tries to set value of Low alarm
less than Zero Value, error message will be displayed.
If (Low Alarm< Zero valu
e), “error” message appears.
High-Alarm value should be greater than Full-scale value. . If user tries to set value of
High-alarm greater than Full-scale value, error message will be displayed.
If (High Alarm > full-
scale value), “error” message appears.
Set point and pre-warn:
Error message will be displayed if, set point value is lower than pre-warn and vice versa.
Alarm ON-OFF :
Using these settings, user can set alarm/relay availability. If particular relay is set as
„yes‟, that particular alarm indication will be present over the display card and relay action
will come into effect.
No.
Name
Description
No of
digit
Lo
limit
Hi limit
1
Low Alarm
Alarm
conditions for
flow rate.
6
0
999998
2
High Alarm
6
0
999999
3
Pre warn
Alarm
Batch control
values.
6
0
999998
4
Set Point
Alarm
6
0
999999
5
rEL1
(Relay 1)
Low alarm /Pre-warn/no
6
rEL2
(Relay 2)
High alarm /Set Pnt /no
7
Filter no
2
4
25