1
User Manual
33
Flow Indicator Totaliser 1006H
REF NO:m16Aom101
Issue No: 03
11. MISCELLANEOUS
RETRAMISSION OUTPUT TABLE FOR OPEN /OVER /UNDER
CONDITION:
For 4-20mA:-
INPUT FEED
(mA)
DISPLAY
RX O/P (mA)
LINEAR
SQUARE
ROOT
LINEAR
SQUARE
ROOT
I/P <1.60
OPEN
OPEN
4.00
4.00
1.60<I/P<3.20
UNDER
UNDER
4.00
4.00
3.20<I/P<4.00
Flow Rate
Flow Rate
4.00
4.00
20.00>I/P>20.80
Flow Rate
Flow Rate
20.00
20.00
20.80>I/P>22.40
OVER
OVER
20.00
20.00
22.40>I/P
OPEN
OPEN
20.00
20.00
NOTE:-
For OPEN Sensor Condition Pre-warn and batch total (Set Point) Relays are in OFF
State.