AI-702M/704M/706M HIGH PERFORMANCE INTELLIGENT 

MULTI-CHANNEL INDICATORS 

Operation Instruction Version 7.6 

 

(Ideal for measurement, indication, alarm, calculation and retransmission of 

temperature, pressure, flow, level, humidity etc.) 

 

 

 

SUMMARY: 

AI-702M, AI-704M and AI-706M multi-channel indicators provide 1-2, 1-4, 1-6 channels of 
independent process indications, and are ideal for the measurement, indication, alarm, 
calculation and retransmission of temperature, pressure, flow, level and humidity etc.     
 

Features:  

  Programmable and modular inputs.  Multiple input types of thermocouples and RTDs, 

voltage/current inputs and two-wire transmitters are field- selectable.     

  Every channel can have independent input specification.  All channels are equipped 

with digital adjustment and digital filtering functions and each channel can set different 
digital adjustment and filtering parameters. 

  High performance hardware design, greatly decreased the temperature drift and the 

interference between channels, thus multi-channel measurement accuracy is 0.2% full 
scale, the same as that of single channel. 

  Provide high accuracy compensation function such as ice-point compensation, copper 

resistance compensation and thermostat compensation to thermocouple inputs.   

  Provide accurate internal calculation functions including addition, extraction, and 

multiplication. 

  Support up to 2 isolated retransmission output.    Any input channel can be retransmitted 

to OUTP port or all channels are cyclically retransmitted. 

  Provide manual/auto pilot display, with 2 pilot speed selectable. 

  Support up to 7 on-off signal inputs/outputs which can work as alarm output or on-off 

signal I/O for host computer. 

  Every input channel has independent low/high limit alarm which can be assigned any 

alarm output. 

  Advanced communication function.  Provide high accuracy and stability multi-channel 

analog data sampling function to host computer.    The host computer can also input up 
to 7 channel on-off signal or execute on-off operation through an indicator. 

  Allow to define up to 12 field parameters, and user can freely customize the instrument. 

  Multiple dimensions are selectable. 100~240VAC universal power supply. 

  Achieved ISO9001 and CE certificates, comply with EMC standard, high reliability and 

stability.  The power and I/O terminals have passed the anti-interference test of 
4KV/5KHz burst of pulses. 

 

Summary of Contents for AI-702M

Page 1: ...l Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Provide accurate internal calculation fun...

Page 2: ...sion 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows...

Page 3: ...nsient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Ph...

Page 4: ...that provides 24VDC power supply Connect to 4 20mA two wires transmitter z Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm i...

Page 5: ...Response time 1 5 seconds if digital filter parameter is set as 0 or 1 z Automatic pilot time interval Approx 1 2s or 2s configurable z Alarm function High and low alarm configurable separately for e...

Page 6: ...on Two wire RTD wiring RTD can select two wire or three wire method by B of AF parameter Two wire method enable to input two channel signals in one module but user has to measure and calculate the res...

Page 7: ...ter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The l...

Page 8: ...means no communication and no alarm it can be treated as normal z The light flashing with period 0 6 second means no communication and general error occurs z The light quickly flashing with period 0...

Page 9: ...put spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re t...

Page 10: ...IL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then t...

Page 11: ...nction selection AF is used to select advanced function The value of AF is calculated as below AF Ax1 Bx2 Cx4 Dx8 Ex16 A 0 Slow cyclic display A 1 Fast cyclic display Above setting only affects displa...

Page 12: ...ansmission current 0 220 Po Atmospheric pressure Defined atmospheric pressure when dry bulb wet bulb humidity measurement was activated Unit KPa 1 120 0 SPEd Wind speed Defined wind speed when dry bul...

Page 13: ...AL1 L AL1 etc Parameters from EP1 to EP12 can define 12 field parameters at most if the number of field parameters is less than 12 sometimes even none it is necessary to define field parameters from...