1
User Manual
19
Flow Indicator Totaliser 1006H
REF NO:m16Aom101
Issue No: 03
8.3.1 Run Mode Parameters Details
No
.
Name
Description
Max digits
Limits
1
Batch
Total
This parameter
displays the Total
flow since batch is
started („BT‟)
Max. 6
0 - 999999
2
Integrated Total
This parameter
displays the Total
flow since Last
Reset. („IT‟)
Max. 6
0 - 999999
3
Roll
Count
This parameter
displays the roll over
count of the
Integrated Total from
„999999‟ to „0‟ („rc‟)
Max. 4
0 - 9999
Batch total:
This is an eight digit totalized value, displayed as Batch total. As per the selected time
base, Zero and Full-scale settings, this total is updated continuously, proportional to input.
When New Batch Starts or Integration total is reset this value also gets initialized to 0.
Integration total:
This is an eight digit totalized value, displayed as integrated total. As per the selected
time base, Zero and Full-scale settings, this total is updated continuously, proportional to
input.
Rollover Count (RC):
This is a two-digit value, displayed as the rollover that takes place when integrated total
gets higher than higher limit. When the integrated total crosses high limit, this count is
incremented by one.
So the total integration will be equal to
(Rollover Count) x (hi limit + 1) + Integrated Total (It)
Integrated total, batch total and roll count are cleared by special password.
On power fail detection, current value of Batch total, integrated total and rollover count
are stored in NVRAM.
Next section will describe the different Item of individual submenu.
Start & Stop function:(In Run Mode)
START key
:
If this key pressed batching relays (WP/EP) gets ON & BATCH TOTAL = 0.It
means a new batch is started. If START key is pressed again and again, it will not
start the batch until WP/EP relays gets OFF.
Relays get OFF by two ways:
1. STOP key
2.
BATCH TOTAL crosses the value of SETPOINT.
STOP
key
:
If user presses
STOP
key in running batch, batching relays (WP/EP) gets off. If
again
STOP
key is pressed again and again only batching relays gets ON/OFF