15
Model
6K
10K
Protective earthing conductor
Min cross section
6mm^2 (8AWG) 75°C type
16mm^2 (4AWG) 75°C type
Input L, N, G
Min conductor cross section
6mm^2 (8AWG) 75°C type
16mm^2(4AWG) 75°C type
Input Breaker
63A
100A
Output L,N,
(
HV mode or LV-2 mode
)
Min conductor cross section
4mm^2 (10AWG) 75°C type 10mm^2(6AWG) 75°C type
Output L,N,
(
LV-1 mode
)
Min conductor cross section
10mm^2 (6AWG) 75°C type 25mm^2(2AWG) 75°C type
Jumper wire
(
for parallel system
)
6mm^2 (8AWG) 75°C type
16mm^2(4AWG) 75°C type
It is recommended that an external isolating device should be installed between the
mains input and UPS as shown in Figure
AC Contactor: 208-240V, 63A (6 kVA)
208-240V, 100A (10 kVA)
3.4.2 Wiring for AC Cable (AC source to UPS)
High leakage current:
Earth connection essential before connecting supply.
Common input/output sources connection.
This type of connection must be carried out by qualified electrical person.
Before carrying out any connection, check that the upstream protection devices
(Normal AC source and Bypass AC source) are open "O" (Off).
Always connect the ground wire first.