background image

C

HIMNEY

  C

AP

  I

NSTALLATION

18

M

ODEL

 LC C

HIMNEY

 C

AP

S

PECIAL

 N

OTE

The proper height as previously explained is important to assure proper draft and safety.  The

chimney cap extends the flue outlet four inches above the top of the last section of chimney.  This should be
kept in mind when determining the proper height for the chimney.  The chimney should not be extended more
than 90 inches above the supporting roof structure without additional support.  In the case of an “A” frame type
construction or other steep pitch roofs that require more than 90 inches of chimney above the roof, a support
should be attached to the chimney at the 90 inch level that is strong enough to support a wind load of 3-1/8
pounds for each inch the chimney extends above 90 inches.  The flue outlet must be a minimum of three feet
above the point where in penetrates the roof.

C

AUTION

:  Be careful to avoid electrical shock hazard when contacting wires to the metal chimney components.

1. Extend the regular chimney sections until the top of the chimney is 4 inches below the total flue height

desired.  Do not snap the last section of inlet air duct or largest diameter pipe in place until Step 3 is
completed.

2. Remove the shingles from around the chimney so that the flashing may be installed, with the upper part of

the flashing under the shingles.

3. Set the flashing on the roof.  Hold a section of the outside pipe (13" diameter) on the flashing and scribe a

line around the flashing, then cut the top off the flashing by cutting 1/4 inch below the scribed line.  This
should increase the diameter of the flashing outlet sufficiently to allow the flashing to be placed over the
chimney.  See Figure 21.

4. Snap the last section of inlet air duct in place and slide the flashing over the chimney.  Adjust the chimney

to assure that the proper minimum clearances are maintained.

5. Nail the flashing securely in place with eight nails.

6. Seal the crack between the top of the flashing and the chimney with mastic.  Leave some excess mastic at

this area to be used in step eight.  NOTE:  Use pliers and wear gloves when performing step seven to
minimize the danger of cutting your hands on the edge of the storm collar.

7. Place the storm collar around the chimney and put the collar together like a belt in belt loops.  Slide the end

of collar under the two loops on the other end with the loops facing up.  Overlap the ends of the collar until
it is tight against the chimney.  Bend the free end of the collar back over the loops to hold the storm collar
securely together.  The excess end of the storm collar may be trimmed off.

8. Slide the storm collar down snugly against the flashing until the excess mastic left in step six is forced up

into the crack between the storm collar and the chimney.  This should make the joint between the flashing
and the chimney watertight.

9. Install the chimney cap by placing the cap into matching parts of the last chimney section.  Then punch or

drill 1/8 inch diameter holes in the inlet air duct (chimney pipe) where specified on the brackets and fasten
it down with the No. 8 screws provided.  Do not penetrate the inner stainless steel pipe while installing the
screws.

10. Check all the parts of the fireplace, chimney and chimney termination cap to assure that no parts have

been damaged or bent during installation and that all parts have been installed properly.

N

OTE

 The metal used for the chimney cap has a rust protective coating but the cut edges of the parts are not

protected.  To prevent rusting and rust staining of nearby structures, exposed parts of the chimney and chimney
cap should be detergent washed and painted with a galvanized primer paint.

53D9028. Rev 1 03/03

Summary of Contents for SB5400SS

Page 1: ...S MODEL RESIDENTIAL AND OUTDOOR FIREPLACE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS FIREPLACE IS LISTED BY OMNI TEST LABORATORIES FOR USE WITH L SERIES CHIMNEY SYSTEM COMPONENTS 53D9028 Rev 1...

Page 2: ...re to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and property damages It is very i...

Page 3: ...areas INTENDED PRODUCT USAGE The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with clearances to combustible building materials specified in this manual...

Page 4: ...mper When the fireplace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the chimney NOTE It is norma...

Page 5: ...30 ELBOWS 21 FT MN HEIGHT 4 30 ELBOWS 86FT MAX HEIGHT CHIMNEY SUPPORT EVERY 25 FT FIRESTOP MODEL LF FS 2 REQUIRES 17x17 FRAMING 54 STORM COLLAR MODEL LC CHIMNEY CAP ROOF FLASHING MODEL 612 CAUTION DO...

Page 6: ...DOORS ARE INSTALLED APPLIES WHEN GLASS DOORS ARE INSTALLED SAMPLE INSTALLATION FOR REFERENCE ONLY EXTERIOR FINISH MATERIALS REMOVED FOR CLARITY FIGURE 2 TOP EDGE OF FIREPLA OP EDGE OF FIREPLACE CE CO...

Page 7: ...6 L 3 6 L 4 8 L 1 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36...

Page 8: ...and some suggested fireplace locations When selecting a location choose one that is away from frequently opened doors central heat outlets or returns or other places where air movements may disturb t...

Page 9: ...ments under or near trees or above the roof of a single story wing of a two story building as shown by Figure 9 All these conditions can cause turbulence or pressure conditions that can cause poor chi...

Page 10: ...EIGHT STORM COLLAR FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGH...

Page 11: ...ng on it and insulating qualities equal to or better than the 1 2 covering provided by the H2068 20 MIN 6 MIN 12 MIN 12 MIN BRICK OR STONE HEARTH EXTENSION 68 LONG MIN SAFETY STRIP IS REQUIRED WHEN UN...

Page 12: ...o another is as follows C K divided by the material thickness Example C 43 divided by 1 2 50 C 86 K C multiplies by the material thickness Example K 86 multiplied by 1 2 50 K 43 R The material thickne...

Page 13: ...l 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flash...

Page 14: ...fireplace and chimney CHIMNEY INSTALLATION In order to assure safe and satisfactory performance of the fireplace it is very important to properly install the chimney This is an important part of the...

Page 15: ...the snap locks engage Continue the process adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sided As the chimney sections are in...

Page 16: ...1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC...

Page 17: ...to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Determine the location and amou...

Page 18: ...HIMN CLEARANCE AT JOIST L SERIES CHIMNEY CONTINUE CHIMNEY THROUGH ROOF AN CONTINUE CHIMNEY THROUGH ROOF AND INSTALL ROUND CHIMNEY CAP OR CHIMNEY HOUSING FIRESTOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE...

Page 19: ...he flashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the flashing securely in place with eight nails 6 Seal the crack between the top of t...

Page 20: ...SET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 INTERMEDIATE INTERMEDIATE SECTIONS S...

Page 21: ...flue pipe and lower it down until the 3 cap legs rest on the top edge of the outer telescope pipe Secure legs of cap to the telescope with screws provided 7 Check all parts of the chimney and chimney...

Page 22: ...NST FIREBOX WALL AND GASKET STEP 1 SECURE OUTSIDE AIR STARTING COLLAR TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKE...

Page 23: ...he assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly should never be mounted in a garage or storage area where combustible fum...

Page 24: ...of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum efficiency and safety Do not use a combustible duct Always us...

Page 25: ...1 11 2 unvented room heater is installed in this fireplace a H2853 CANOPY must also be installed WARNING Do not operate an unvented gas log set in this fireplace with the chimney removed The installer...

Page 26: ...the fireplace face Seal the face of the fireplace to the surrounding wall with non combustible caulk or trim materials to prevent cold air leakage around the fireplace The trim should not block or res...

Page 27: ...E MANTEL USTIBLE MANTEL USE ONLY NON COMBUSTIBLE MATERIALS BELOW W TOP OF SPACERS COMBUSTIBLE FRAMING MEMBERS TO TOP OF SPACERS 12 MAX MAX 18 MIN FROM FIREPLACE OPENING TO BOTTOM OF COMBUSTIBLE MANTEL...

Page 28: ...a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well when...

Page 29: ...s doors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to make a good fire...

Page 30: ...reosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection maintenance and cleaning by removing th...

Page 31: ...f the fireplace 4 Do insulate the exterior walls surrounding the fireplace to prevent excessive heat loss from the fireplace 5 Do trim the face of the fireplace only with noncombustible materials 6 Do...

Page 32: ...articles near the fireplace 15 Don t store or place flammable liquids gases or pressurized containers near the fireplace 16 Don t neglect to instruct all responsible persons in the proper and safe op...

Page 33: ...R FIREBRICK BACK ASSEMBLY FIREBRICK RT SIDE ASSEMBLY HEARTH REFRACTORY KEY NO 1 2 3 4 5 6 7 8 9 10 FIGURE 28 53D9028 Rev 1 03 03 All repair part orders should be placed through your local dealer To en...

Page 34: ...onents Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout...

Page 35: ...Contact the nearest dealer If you cannot locate your dealer call or write Martin Hearth Heating as indicated below 2 If you do not receive satisfactory service from the dealer within a reasonable time...

Page 36: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE 53D9028 REV 1 03 03...

Reviews: