AC power
15
When installing an Amphenol C016 series power connector in a 2-phase system:
- Fasten the green/yellow ground (earth) conductor in the screw terminal marked
Drain
or
.
- Fasten the black phase 1
conductor in the screw terminal marked
1
.
- Fasten the white phase 2
conductor in the screw terminal marked
3
.
- Do not connect anything to the terminal marked
2
.
6. Tighten the internal strain relief clamp onto the cable.
7. Tighten the back shell onto the male or female contact insert.
8. Tighten the cable nut onto the back shell.
Power plugs and power outlet sockets
A power plug must be installed on the power input cable so that
you can connect LC Plus panels to AC mains power. Install a
grounding-type (earthed) industrial 3-prong type B plug (see
Figure 10) that complies with IEC 60309 or a comparable national
standard and is rated 16 A minimum, and use corresponding
power outlet sockets. Follow the plug and socket manufacturer’s
instructions and all locally applicable laws and electrical safety
codes.
When installing a power plug in a single-phase system:
• Connect the green/yellow ground (earth) conductor to the
terminal marked
or
.
• Connect the brown live conductor to the terminal marked
L
.
• Connect the blue neutral conductor to the remaining terminal.
When installing a power plug in a 2-phase system:
• Connect the green ground (earth) conductor to the terminal marked
or
.
• Connect the black phase 1 conductor to the terminal marked
L
.
• Connect the white phase 2 conductor to the remaining terminal.
Wire color
(EU color code)
Wire color
(US color code)
Pin
Symbol
Screw (US)
brown
black
live
L
yellow or brass
blue
white
neutral
N
silver
yellow/green
green
ground (earth)
or
green
Table 1: Wire colors and pin identification
Figure 10: Industrial IEC 60309 type
B power plug