background image

 18

Exterior 400 Image Projector user manual

Control data link

Exterior 400 Image Projector fixtures must be connected via a control data link for DMX controller or 
synchronized (master/slave) operation.The following considerations must be taken into account when 
planning the data link:
• RS-485 data cable designed for exterior use is required for outdoor installations. RS-485 cable has low 

capacitance and a characteristic impedance of 85 to 150 Ohms. It is electrically shielded and has at least 
1 twisted pair of conductors. The minimum recommended wire size is 0.25 mm

2

 (24 AWG) for runs up to 

300 meters (1000 ft.) and 0.32 mm

2

 (22 AWG) for runs up 500 meters (1640 ft). CAT 5 network cable 

designed for direct burial can be used in outdoor installations, but you are recommended to run it inside 
conduit.

• The maximum permitted control data cable length before a control signal amplifier is required is 500 

meters (1640 ft.).

• Fixtures must be ‘daisy-chained’, i.e. the data cable must be connected in one single chain of fixtures as 

shown in Figure 8 on page 15.

• Each chain may connect a maximum of 32 fixtures. After this the signal must be amplified.
• An optically isolated amplifier-splitter such as the Martin DMX 5.3 Splitter™ (P/N 90758140) or Martin 

RDM 5.5 Splitter™ (P/N 90758150) must be used to:

- extend a link beyond 500 meters (1640 ft.)
- extend the link to include a further maximum 32 fixtures, or
- branch the link into further single chains, each containing 32 fixtures. The Martin Splitters mentioned 

above allow a link to be branched into five new chains.

• Each chain on the link must be terminated by placing a 120 ohm resistor (available from Martin, 

P/N 04150308) across the data hot (+) and cold (-) conductors of the last fixture on the chain.

• Long parallel runs of AC power and control data cables may cause interference on the data link and must 

be avoided. Even if not required by law, use separate conduits for power and data cables.

• One DMX universe has 512 DMX control channels available. If individual control of the fixtures in an 

installation is required, each fixture must be given its own channels until the limit of 512 is reached. At this 
point, a new DMX universe must be created before more fixtures can be added. 

• An Exterior 400 Image Projector requires nine DMX channels. The total number of Exterior 400 Image 

Projectors that can be linked in one DMX universe will therefore be 512 / 9 = 56 (note that an 
amplifier-splitter must be used each time the limit of 32 devices on one branch is reached).

Connection pinouts

XLR connection

XLR connectors are suitable if DMX cable is used for the data link. XLR pin numbers are normally marked 
on connectors. Connectors must be wired using the standard DMX/RDM pin-out:
• Pin 1: Cable shield
• Pin 2: DMX/RDM Data 1 - (cold)
• Pin 3: DMX/RDM Data 1 + (hot)
Pins 4 and 5 on 5-pin XLR connectors are not used by DMX or RDM signals but are available for special 
Data 2 connections. If used, they must be wired as follows:
• Pin 4: Data 2 - (cold)
• Pin 5: Data 2 + (hot)
To avoid ground/earth loop interference, ensure that the DMX cable shield does not come into contact with 
the shell or body of XLR connectors.

RJ-45 connection

RJ-45 connectors are suitable if CAT 5 cable is used for the data link. RJ-45 cable connector pins are 
numbered from the left looking at the face of the connector with the locking clip on top (see Figure 9). 
Connectors must be wired according to the 568-B system using the standard RJ-45 pin-out for DMX 
applications:
• Pin 1 (White/orange): DMX/RDM data hot (+)
• Pin 2 (Orange): DMX/RDM data cold (-)

Summary of Contents for Exterior 400

Page 1: ...user manual Exterior 400 Image Projector...

Page 2: ...or any other loss occasioned by the use of inability to use or reliance on the information contained in this manual The Martin logo the Martin name and all other trademarks in this document pertaining...

Page 3: ...eapplied deliberately or accidentally before carrying out any installation or maintenance work Disconnect the fixture from AC power before removing or installing any cover or part and when not in use...

Page 4: ...ar optical instruments that may concentrate the light output Ensure that persons are not looking at the LEDs from within 8 3 m 27 3 ft when the product lights up suddenly This can happen when power is...

Page 5: ...orientation 13 Fastening to a surface 13 Tilt adjustment 14 Power and DMX data cable layout 15 AC mains power 16 Connecting to power 16 Control data link 18 Connecting the data link 19 Effects 20 Fixt...

Page 6: ...er supply unit with 100 240 VAC 50 60 Hz operating range Remote configuration and addressing over the DMX data link For the latest photometric data firmware updates documentation product specification...

Page 7: ...void contaminating them with dirt and grease especially from your fingers and follow these precautions 1 Use clean dry lint free gloves when handling optical parts such as filters and gobos 2 To give...

Page 8: ...nt cover B then remove the front cover B and front cover seal C from the fixture housing F 4 Using a T bar or long Allen key reach down into the housing and remove the four effects module retaining sc...

Page 9: ...alled push it away from the color wheel towards the gobo wheel slightly to release it then grasp it by the edges and remove it If your fingers are too large protect the glass with a piece of paper tha...

Page 10: ...LEDs Less reflective side away from LEDs The less reflective side of a coated gobo will absorb less heat if it faces away from the LEDs To determine which side of a gobo is coated hold an object up t...

Page 11: ...ool Push the goboholder in until it snaps into place in its cutout in the gobo wheel Replacing gobos in goboholders Gobos in rotating goboholders are interchangeable and can be replaced with gobos eit...

Page 12: ...e and front cover 1 Lower the effects module into position in the housing Note the number of pins in the multi connectors to the module and reconnect them 2 See Figure 1 on page 8 Using a T bar or lon...

Page 13: ...it in water or any other fluid Do not install it in a location where flooding may occur Ensure sufficient drainage to cope with the heaviest rainfall Make sure that water can drain away from the insta...

Page 14: ...h slots C to secure the fixture Installing bolts through slots C will give approximately 90 of pan adjustment If additional bolts are required to mount the fixture safely install bolts through holes B...

Page 15: ...e opto splitter is required OPTO SPLITTER DMX Universe 1 Universe 1 DMX Universe 2 AC power Fixture Fixture Fixture Figure 8 Schematic cable layout diagram OPTO SPLITTER Power 230V AC 50 Hz Power 230V...

Page 16: ...system at 100 240 V nominal 50 60 Hz Terminal blocks or suitable connection devices must be provided by the installer Danger Lock out power to the entire installation before working on cables and con...

Page 17: ...lug that is suitable for local AC mains power outlets and approved for the installation environment on the supplied power cable If you choose to do this install a grounding type earthed plug that is r...

Page 18: ...cross the data hot and cold conductors of the last fixture on the chain Long parallel runs of AC power and control data cables may cause interference on the data link and must be avoided Even if not r...

Page 19: ...power and data cables may be installed or replaced only by Martin or its authorized service agents The fixture is supplied with a 1 8 meter 5 9 ft data cable tail for data connection The cable contain...

Page 20: ...oothly from 100 to zero Note that four different dimming curves can be selected using the Martin MUM application see Dimming curve options on page 23 or via DMX on the fixture control channel 9 Color...

Page 21: ...Refer to the MUM user manual for instructions on installing and starting the MUM application Connecting a PC with MUM To connect a PC running MUM to an Exterior 400 Image Projector 1 Obtain the Martin...

Page 22: ...controller on a group of DMX channels that are not used by any other device in its DMX universe The DMX address also known as the control address or start channel is the first of these channels Each...

Page 23: ...is disabled to prevent accidental resets 5 Sec A reset command sent on DMX channel 9 must be sent for five seconds to reset the fixture Dimming curve options The Dimming Curve setting provides four di...

Page 24: ...patible with RDM Remote Device Management Using an RDM compliant DMX controller such as the Martin M PC Windows application you can communicate with all the fixtures on a data link via RDM without nee...

Page 25: ...from the effects of low temperature Starting a fixture that is below 0 C 32 F may cause damage to moving parts that is not covered by the product warranty DMX control The industry standard DMX system...

Page 26: ...ur period Enabling stand alone operation To enable stand alone operation set Stand alone operation to Enabled Starting automatically To set stand alone operation to start automatically set Auto progra...

Page 27: ...tton 2 In the Gobo section clicking on a number to select a gobo slot and move the Rotate fader to select rotation direction and speed 3 In the Intensity section move the fader to the desired output i...

Page 28: ...erates in stand alone mode independently of other fixtures Master Sends trigger signals to other fixtures or Synchronized Sets fixture as a slave that receives trigger signals from a master fixture No...

Page 29: ...f a slave has fewer scenes than the master it will derive which scene to go to by dividing the number of the scene it has been commanded to go to scene 5 for example by the total number of scenes that...

Page 30: ...scenes 0 and 2 on the slave are longer than the corresponding scenes on the master M master S slave F fade W wait Time Programmed M0 M1 M2 Master F W F W F W S0 S1 S2 Slave F W F W F W Result M0 M1 M2...

Page 31: ...characteristics are affected by wear and tear after an extended period of use and if you require fixtures to perform within very precise optical and color parameters Cleaning Regular cleaning is esse...

Page 32: ...he current ambient temperature Fan readouts display the current internal and external cooling fan speeds in RPM revolutions per minute Software installation It may be necessary to upload new software...

Page 33: ...dicator LEDs Two LEDs on the rear cover give information about fixture status LED 1 DMX data status Lights steady red if the fixture receives data it cannot recognize Lights steady green when the fixt...

Page 34: ...r Open Strobe 9 fast slow Electronic Sinewave Shutter Open Strobe 10 fast slow Electronic Burst Shutter Open Snap 20 2 0 255 0 100 Intensity fade Zero full Fade 0 3 0 1 15 16 17 31 32 33 47 48 49 63 6...

Page 35: ...o rotation speed on channel 5 CW fast slow CCW slow fast Snap 0 5 0 255 0 125 126 128 129 255 0 100 0 48 49 50 51 100 Gobo indexing and rotation select gobo on channel 4 Indexed position 0 395 Continu...

Page 36: ...ddressing Check fixtures DMX addresses Fixture defective Have faulty fixture serviced by Martin service technician Other device on DMX link defective Bypass devices on DMX link until the faulty device...

Page 37: ...in stand alone mode Optics Light source 7 x Luminus CBT 90 50 W LEDs White LED 6500 K Minimum LED lifetime 60 000 hours to 70 luminous output Manufacturer s figure obtained under manufacturer s test...

Page 38: ...imum ambient temperature Ta max 45 C 113 F Minimum ambient temperature Ta min 30 C 22 F Maximum surface temperature steady state Ta 40 C 65 C 149 F Total heat dissipation calculated 10 1570 BTU hr Pow...

Page 39: ...010 Martin M PC Basic up to 8 DMX universes incl USB Duo interface box P N 90732070 Martin USB Duo USB DMX interface box P N 90703010 Ordering Information Exterior 400 Image Projector Narrow EU model...

Page 40: ......

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...www martin com Olof Palmes All 18 8200 Aarhus N Denmark Tel 45 8740 0000 Fax 45 8740 0010...

Reviews: