background image

9

Safety 

Precautions

Page 9

8.

Repair to intrinsically safe components

:

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will

 

not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe

 

components are the only types that can be worked on while live in the presence of a flammable

 

atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts

 

specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere

 

from a leak.

9.

Cabling

:

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or

 

any other adverse environmental effects. The check shall also take into account the effects of aging or

 

continual vibration from sources such as compressors or fans.

10.

Detection of flammable refrigerants

:

Under no circumstances shall potential sources of ignition be used in the searching for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

11.

Leak detection methods

:

The following leak detection methods are deemed acceptable for systems containing flammable

 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity

 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a

 

 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for

 

the 

refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant

 

 

and 

shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %maximum) is 

confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of

 

detergents 

containing chlorine shall be avoided as the chlorine may react with the refrigerant and

 

corrode the 

copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished.

 

If a leakage of 

refrigerant is found which requires brazing, all of the refrigerant shall be recovered from

 

the system, or 

isolated (by means of shut off valves) in a part of the system remote from the leak.

 

Oxygen free nitrogen 

(OFN) shall then be purged through the system both before and during the

 

brazing process.

12.

Removal and evacuation

:

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional

 

procedures shall be used. However, it is important that best practice is followed since flammability is a

 

consideration. The following procedure shall be adhered to:
Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the

 

circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed

 

with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or

being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 
electrical supply to equipment during servicing, then a permanently operating form of leak detection 
shall be located at the most critical point to warn of a potentially hazardous situation. 
2)Particular attention shall be paid to the following to ensure that by working on electrical components,
the casing is not altered in such a way that the level of protection is affected. This shall include damage
to cables, excessive number of connections, terminals not made to original specification, damage to
seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or
sealing materials have not degraded such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated prior to working on them.

Summary of Contents for PS-101B

Page 1: ...www marsdelivers com Owner s Manual Installation Manual Portable Air Conditioner PS 81B PS 101B...

Page 2: ...recautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaus...

Page 3: ...the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and vibra...

Page 4: ...he appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply power cord is damaged it must be replaced by the man...

Page 5: ...ntact a qualified person to carry out repairs If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired Hold the plug by th...

Page 6: ...ce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Please follow the instructions carefully to handle install clear a...

Page 7: ...system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General work are...

Page 8: ...ly into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufac...

Page 9: ...the copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from t...

Page 10: ...actice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant...

Page 11: ...ructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good workin...

Page 12: ...cedure not to the portable air conditioners themselves The energy rating and noise information for this unit is based on the standard installation using and un extended exhaust duct without window sli...

Page 13: ...etermine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amo...

Page 14: ...ose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 set 1 pc Window Slider B Remote Controller and...

Page 15: ...sliders once they are adjusted to the Proper length Window slider A Window slider B Bolt Window slider A Window slider B Window slider C Bolts Step Two Install the Exhaust hose assembly to the unit Pu...

Page 16: ...sash and frame as shown Foam seal B Adhesive type shorter Foam seal A Adhesive type Or Or Window slider A Window slider B if required Foam seal C Non adhesive type 3 Cut the non adhesive foam seal C s...

Page 17: ...he actual shape shall prevail NOTE Cover the hole using the adaptor cap when not in use max 120cm or 47 inch min 30cm or 12 inch Expansion anchor position Adaptor cap Wall Exhaust Adaptor B Or 5 Inser...

Page 18: ...set temperature while on COOL HEAT or AUTO MODE While on DRY and FAN modes it shows the room temperature Shows Error codes E0 EEPROM error E1 Room temperature sensor error E2 Evaporator temperature s...

Page 19: ...ows AP to indicate you can set wireless connection If connection router is successful within 8 minutes the unit will exit wireless connection mode automatically and the wireless indicator illuminates...

Page 20: ...end of the hose is down to let the water flow smoothly When the continuous drain hose is not used ensure that the drain plug and knob are installed firmly to prevent leakage Continuous drain hose Remo...

Page 21: ...he unit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the ap...

Page 22: ...cian to inspect the unit and top off refrigerant Decrease the set temperature Make sure all windows and doors are closed Double check the cooling area Turn off the unit disconnect the hose check for b...

Page 23: ...warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagno...

Page 24: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: