background image

8

Safety 

Precautions

Page 8 

7.

Repairs to sealed components

:

1)

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment

 The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure 
   the technician is aware of potentially flammable atmospheres. Ensure that the leak detection 
   equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately 
   sealed or intrinsically safe.

5)

Presence of fire extinguisher

:

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate

 

fire 

extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher

 

adjacent 

to the charging area.

6)

No ignition sources

:

No person carrying out work in relation to a refrigeration system which involves exposing any pipe
work that contains or has contained flammable refrigerant shall use any sources of ignition in such a

 

manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette

 

smoking, should be kept sufficiently far away from the site of installation, repairing, removing and

 

disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior
to work taking place, the area around the equipment is to be surveyed to make sure that there are no

 

flammable hazards or ignition risks. No Smoking signs shall be displayed.

7)

Ventilated area

:

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or

 

conducting any hot work. A degree of ventilation shall continue during the period that the work is carried

 

out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into

 

the atmosphere.

8)

Checks to the refrigeration equipment

:

Where electrical components are being changed, they shall be fit for the purpose and to the correct

 

specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in

 

doubt consult the manufacturer's technical department for assistance. The following checks shall be

 

applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing parts are

 

installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence

 

of 

refrigerant; Marking 

on

 the equipment continues to be visible and legible. Markings and signs that

 

are 

illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be exposed
to any substance which may corrode refrigerant containing components, unless the components are

 

constructed of materials which are inherently resistant to  being corroded or are suitably protected

 

against being so corroded.

9)

Checks to electrical devices

:

Repair and maintenance to electrical components shall include initial safety checks and component

 

inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be

 

connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately

 

but 

it is necessary to continue operation, an adequate temporary solution shall be used. This shall be

 

reported 

to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
That there no live electrical components and wiring are exposed while charging, recovering or purging

 

the system; That there is continuity of earth bonding.

Summary of Contents for PS-101B

Page 1: ...www marsdelivers com Owner s Manual Installation Manual Portable Air Conditioner PS 81B PS 101B...

Page 2: ...recautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaus...

Page 3: ...the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and vibra...

Page 4: ...he appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply power cord is damaged it must be replaced by the man...

Page 5: ...ntact a qualified person to carry out repairs If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired Hold the plug by th...

Page 6: ...ce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Please follow the instructions carefully to handle install clear a...

Page 7: ...system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General work are...

Page 8: ...ly into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufac...

Page 9: ...the copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from t...

Page 10: ...actice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant...

Page 11: ...ructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good workin...

Page 12: ...cedure not to the portable air conditioners themselves The energy rating and noise information for this unit is based on the standard installation using and un extended exhaust duct without window sli...

Page 13: ...etermine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amo...

Page 14: ...ose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 set 1 pc Window Slider B Remote Controller and...

Page 15: ...sliders once they are adjusted to the Proper length Window slider A Window slider B Bolt Window slider A Window slider B Window slider C Bolts Step Two Install the Exhaust hose assembly to the unit Pu...

Page 16: ...sash and frame as shown Foam seal B Adhesive type shorter Foam seal A Adhesive type Or Or Window slider A Window slider B if required Foam seal C Non adhesive type 3 Cut the non adhesive foam seal C s...

Page 17: ...he actual shape shall prevail NOTE Cover the hole using the adaptor cap when not in use max 120cm or 47 inch min 30cm or 12 inch Expansion anchor position Adaptor cap Wall Exhaust Adaptor B Or 5 Inser...

Page 18: ...set temperature while on COOL HEAT or AUTO MODE While on DRY and FAN modes it shows the room temperature Shows Error codes E0 EEPROM error E1 Room temperature sensor error E2 Evaporator temperature s...

Page 19: ...ows AP to indicate you can set wireless connection If connection router is successful within 8 minutes the unit will exit wireless connection mode automatically and the wireless indicator illuminates...

Page 20: ...end of the hose is down to let the water flow smoothly When the continuous drain hose is not used ensure that the drain plug and knob are installed firmly to prevent leakage Continuous drain hose Remo...

Page 21: ...he unit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the ap...

Page 22: ...cian to inspect the unit and top off refrigerant Decrease the set temperature Make sure all windows and doors are closed Double check the cooling area Turn off the unit disconnect the hose check for b...

Page 23: ...warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagno...

Page 24: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: