background image

IOM -  

Horizontal/Side Discharge Condensing Units

13

Horizontal/Side Discharge Condensing Units

The length of refrigerant lines and the number of 

bends determine the pressure drop which affects 

capacity and efficiency of the system and oil return 

to the compressor. The outdoor unit connections 

are 

braze

 type. Tube size should always be the 

same diameter as the connections provided at the 

service valves. Up sizing of lines can result in 

inadequate oil return to the compressor and 

excessive refrigerant charge and will void the 

warranty 

[See Table 1].

Choose a location that places the condensing 

unit as close to the indoor unit as possible. The 

maximum separation is dependent on model. 

Use only clean refrigeration grade tubing. Avoid 

piping on wet or rainy days. Always keep the tube 

ends capped until you are ready to make the final 

connections. Remove burrs from cut ends of tubing. 

Use tube benders to avoid kinking.

Insulate the suction line with Armaflex or equivalent 

with a wall thickness of at least 3/8”. Support the 

tubing adequately to avoid sags that can trap oil. 

Isolate the tubing so as not to transmit noise to the 

building structure. Avoid sharp edges that could cut 

the tubes. Maximum vertical lift (compressor above 

evaporator) is dependent on model. Trap risers with 

a ‘P’ trap every 10 feet.

REFRIGERANT PIPING

LEAk TEST, 

EVACUATION 

& RELEASE OF 

REFRIGERANT 

The condensing unit is supplied with R-410a 

charge sufficient for most matching evaporator 

units. Charge must be added for interconnecting 

tubing.

The unit’s service valves are shipped in the closed 

position and should not be opened until final 

connections and evacuation are completed. 

The recommended procedure for leak test, 

evacuation, and release of refrigerant is 

outlined below:

1. Complete the final piping connections to the

indoor and outdoor units using high temperature

brazing alloy.

2. Connect a charging manifold to the service ports

provided at the service valves.

3. Pressurize the lines and evaporator with

nitrogen and leak check all connections with

soap bubbles. Repair as necessary any

faulty joints. If brazing is required be sure to

RELEASE THE NITROGEN FIRST. Re-test as

needed.

4. Connect a vacuum pump to the manifold center

connection, start the pump and open the

manifold valves.

5. Evacuate to 500 microns or less for a minimum

of 30 minutes. Close the manifold valves and

shut off the pump. Note the vacuum reading and

wait 15 minutes. Take a new vacuum reading. A

reading of 800 microns or higher indicates the

presence of moisture or a leak.

6. Repair as necessary and repeat steps 3, 4 & 5.

7. Confirm that manifold valves are closed and

disconnect the vacuum pump.

8. Remove the caps from the services valves.

Open the valves to the fully ‘back-seat’ position.

Replace service valve caps and tighten.

WARNING

It is illegal to discharge refrigerant into the 

atmosphere. Use proper reclaiming methods 

and equipment when working on the refrigerant 

containing parts of the unit. Service should be 

performed by a QUALIFIED service agency and 

certified technicians.

*Minimum pipe length must not be less that 15 feet.

** “P” trap risers every 10 ft. when outdoor unit is installed

above indoor unit.

Summary of Contents for Comfort-Aire CMA1412SG-0

Page 1: ...17 787 2100 www marsdelivers com Installation Operation and Maintenance Manual Horizontal Side Discharge Condensing Units Models CMA1412SG 0 CMA1418SG 1 CMA1424SG 1 CMA1430SG 1 CMA1436SG 1 CMA1448SG 1...

Page 2: ...ion Operation and Maintenance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 12 Wiring Diagrams 8 12...

Page 3: ...efrigeration cycle explosion and injury 8 Do not modify the length of the power supply cord or use an extension cord and do not share the single outlet with other electrical appliances Otherwise it ma...

Page 4: ...imes per hour If you notice more frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not rai...

Page 5: ...uctless air handlers may be used but often do not include an expansion device A properly sized thermostatic expansion valve is recommended Consult AHRI s directory of certified products for indoor mat...

Page 6: ...r snow or ice may fall from a roof onto the unit In climates where snow is a consideration locate the unit away from areas prone to drifting Ensure the location of the unit will not be subject to snow...

Page 7: ...e maintained to ensure that the air inlets and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5...

Page 8: ...ll likely result in failure of the compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rated voltage of the air conditioner not to exc...

Page 9: ...tinued NOTE1 Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional wiring instructions TERMINAL bLOCk OF OUTDOOR UNIT TERMINAL bLOCk OF...

Page 10: ...Horizontal Side Discharge Condensing Units 10 Horizontal Side Discharge Condensing Units OUTDOOR UNIT WIRING CONNECTION continued 12K 18K NOTE For reference only the actual wiring diagram shall preva...

Page 11: ...IOM Horizontal Side Discharge Condensing Units 11 24K 30K NOTE For reference only the actual wiring diagram shall prevail 36K...

Page 12: ...IOM Horizontal Side Discharge Condensing Units 12 48K Horizontal Side Discharge Condensing Units 12 NOTE For reference only the actual wiring diagram shall prevail...

Page 13: ...added for interconnecting tubing The unit s service valves are shipped in the closed position and should not be opened until final connections and evacuation are completed The recommended procedure fo...

Page 14: ...s a reference to ensure performance 2XWGRRU PELHQW 7HPSHUDWXUH 96 3UHVVXUH 2XWGRRU 7HPSHUDWXUH 1RWH 7 QGRRU 7HPSHUDWXUH 2 7 2XWGRRU 7HPSHUDWXUH 5HPRYH UHIULJHUDQW LI WKH SUHVVXUH LV DERYH WKH FKDUW YD...

Page 15: ...umer The consumer must retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITE...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: