background image

IOM -  

Horizontal/Side Discharge Condensing Units

4

4

Horizontal/Side Discharge Condensing Units

OPERATING INSTRUCTIONS

Air conditioners are designed to provide comfort 

cooling at outside temperatures above 65°F 

(18°C) but less than 109°F (43°C). Operating the 

air conditioner outside of this temperature range 

may cause unit failure and will void the warranty. 

If you have need for cooling at lower outdoor 

temperatures a “low ambient co

ntrol

” can be field 

installed. Contact your local contractor or call the 

factory.

TO OPERATE:

NOTE:

 

The thermostat operation may vary 

by type and model used. Please consult the 

operating manual that was provided with 

the thermostat. The instructions below are 

generalized for most standard thermostat 

models.

1. Set the switch on your wall thermostat to the

‘cool’ position.

2. Set the desired temperature (between 63-86°F

or 17-30°C) you want to maintain by moving the

temperature setting on your thermostat. If the

room is warmer than the setting, the unit will

turn on and begin to blow cool air after a few

minutes. A warm, humid room or building may

take several hours of continuous operation to

cool to the thermostat set point the first time.

Once the set temperature is reached the unit

will cycle on and off.

3. Set the ‘Fan’ switch on the thermostat to ‘auto’

if you want the fan to run only when cooling

is needed or to ‘on’ if you want continuous

air circulation. The ‘on’ setting of the fan

generally provides better temperature control by

eliminating stagnant air.

NOTE:

 A properly installed and sized unit will 

not cycle more than 10 times per hour. If you 

notice more frequent starts call your service 

contractor.

4. For energy conservation reasons, you may want

to set your thermostat at a higher temperature

when you are away. Do not raise the

temperature setting by more than 5 degrees.

Changing the temperature by more than 5

degrees or shutting the unit ‘off’ can actually

cost more than leaving the setting at a constant

temperature.

IMPORTANT

Wait at least 3 minutes after turning your air 

conditioner off before trying to restart it. This 

gives the unit the time needed to stabilize 

before restarting. Failure to do so may cause 

unit damage and failure.

MAINTENANCE: 

Only simple periodic maintenance is required:

1.

Change or clean the indoor unit air fil

t

er

monthly

 

or more frequently if unusual conditions

are

 

encountered. If you have a disposable type,

throw the old one away and install a fresh one

of the same size and type. If your unit has a

washable type then vacuum and wash with

soap and water. Flush thoroughly and dry

before re-installing.

2.

Keep the coil in the outdoor unit clean.

Periodically flush the coil thoroughly with a

garden hose. Clean away all foreign materials

such as dust, leaves, grass clippings, papers,

etc.

IMPORTANT! 

Alterations and replacement parts:

Altering the product or replacing parts 

with non-authorized parts will void the 

factory Warranty and may result in adverse 

operational performance and/or a possible 

hazardous safety condition to service 

personnel and occupants. If you are in doubt 

as to how to service this unit or where to find 

factory replacement parts, call Heat Controller 

at (517) 787-2100 for assistance.

WARNING

Turn the power off first! Serious injury or death 

may result if water spray is directed at live 

electrical connections or power sources.

Summary of Contents for Comfort-Aire CMA1412SG-0

Page 1: ...17 787 2100 www marsdelivers com Installation Operation and Maintenance Manual Horizontal Side Discharge Condensing Units Models CMA1412SG 0 CMA1418SG 1 CMA1424SG 1 CMA1430SG 1 CMA1436SG 1 CMA1448SG 1...

Page 2: ...ion Operation and Maintenance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 12 Wiring Diagrams 8 12...

Page 3: ...efrigeration cycle explosion and injury 8 Do not modify the length of the power supply cord or use an extension cord and do not share the single outlet with other electrical appliances Otherwise it ma...

Page 4: ...imes per hour If you notice more frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not rai...

Page 5: ...uctless air handlers may be used but often do not include an expansion device A properly sized thermostatic expansion valve is recommended Consult AHRI s directory of certified products for indoor mat...

Page 6: ...r snow or ice may fall from a roof onto the unit In climates where snow is a consideration locate the unit away from areas prone to drifting Ensure the location of the unit will not be subject to snow...

Page 7: ...e maintained to ensure that the air inlets and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5...

Page 8: ...ll likely result in failure of the compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rated voltage of the air conditioner not to exc...

Page 9: ...tinued NOTE1 Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional wiring instructions TERMINAL bLOCk OF OUTDOOR UNIT TERMINAL bLOCk OF...

Page 10: ...Horizontal Side Discharge Condensing Units 10 Horizontal Side Discharge Condensing Units OUTDOOR UNIT WIRING CONNECTION continued 12K 18K NOTE For reference only the actual wiring diagram shall preva...

Page 11: ...IOM Horizontal Side Discharge Condensing Units 11 24K 30K NOTE For reference only the actual wiring diagram shall prevail 36K...

Page 12: ...IOM Horizontal Side Discharge Condensing Units 12 48K Horizontal Side Discharge Condensing Units 12 NOTE For reference only the actual wiring diagram shall prevail...

Page 13: ...added for interconnecting tubing The unit s service valves are shipped in the closed position and should not be opened until final connections and evacuation are completed The recommended procedure fo...

Page 14: ...s a reference to ensure performance 2XWGRRU PELHQW 7HPSHUDWXUH 96 3UHVVXUH 2XWGRRU 7HPSHUDWXUH 1RWH 7 QGRRU 7HPSHUDWXUH 2 7 2XWGRRU 7HPSHUDWXUH 5HPRYH UHIULJHUDQW LI WKH SUHVVXUH LV DERYH WKH FKDUW YD...

Page 15: ...umer The consumer must retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITE...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: