background image

Owner’s Manual -  

Packaged Terminal

8

7

WIRING

Cord connection to a wall socket is not permitted for 

265V units. All 265V units must be hard wired using 

the hard wire kit or make use of the plug in receptacle 

in the standard subbase.

230~208V units are equipped with LCDI  power cords 

and can open the electrical circuit  to the unit. In 

the event the unit does not operate, check the reset 

button located on or near the head of the power cord 

as part of the normal procedure.

VOLTAGE MEASUREMENTS

Once the unit is properly wired, measure the unit

supply voltage. Voltage must fall within the voltage

range given in Chart 3.

Fig. 6 Receptacles / Sub-bases

NOTE:

 See the “Remote Thermostat Change”

Instructions before using the thermostat.

Fig. 7 wall mounted thermostat wiring

Operating Voltage

Unit Voltage

Voltage Utilization Range

Rating

Minimum

Minimum

230/208

187

253

265

238

292

Chart 3 - Operating Voltage

WARNING 

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING OR 

INSTALLING THIS UNIT MULTIPLE POWER SOURCES BE 

PRESENT, FAILURE TO DO SO MAY CAUSE PROPERTY 

DAMAGE, PERSONAL INJURY OR DEATH.

DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING 

OFF THE POWER TO THE UNIT FROM THE CIRCUIT 

BREAKER AND/OR REMOVING THE UNIT CORD SET PLUG 

FROM THE WALL OUTLET.

!

WARNING 

TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL 

INJURY OR FIRE, USE ONLY COPPER CONDUCTORS.

!

WARNING 

TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL 

INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT 

USE AN EXTENSION CORD WITH THIS UNIT.

!

WARNING 

TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL 

INJURY OR FIRE. DO NOT INSTALL WITH POWER CORD 

STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE 

LOOSE PLUG/RECEPTACLE CONNECTION.

!

WARNING 

TO AVOID THE RISK OF PERSONAL INJURY, WIRING TO THE 

UNIT MUST BE PROPERLY POLARIZED AND GROUNDED.

!

WARNING 

THIS AIR CONDITIONER IS NOT MEANT TO PROVIDE 

UNATTENDED COOLING OR LIFE SUPPORT FOR PERSONS 

OR ANIMALS WHO ARE UNABLE REACT TO THE FAILURE 

OF THIS PRODUCT.

THE FAILURE OF AN UNATTENDED AIR CONDITIONER MAY 

RESULT IN EXTREME HEAT IN THE CONDITIONED SPACE 

CAUSING OVERHEATING OR DEATH TO PERSONS OR 

ANIMALS.

!

265V 30 Amp

265V 20 Amp

Large tandem

230/208V 30 Amp

Perpendicular

230/208V 20 Amp

Thermostat

Summary of Contents for Comfort-aire Century PTAC07F130A

Page 1: ...0ASC PTAC12F150ASC PTAC15F130ASC PTAC15F150ASC Heat Pump with Electric Heat with seacoast coating PTHP12F130ASC PTHP12F150ASC PTHP15F130ASC PTHP15F150ASC 7 000 15 000 BTUH Cooling w Electric Heat PTAC...

Page 2: ...ING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 CONTENTS UNIT FEATURES 3 INSTALLATION INSTRUCTION 5 WIRING 8 OPE...

Page 3: ...er the compressor turns off the unit will restart when the pressure turns back below 551 psi This protection can effectively avoid the burst and leakage of pipes lessen the system failures and prolong...

Page 4: ...ntrol functions for DIP switches The DIP switches are on main board NO 4 Heating priority ON Heat pump to be prior OFF Electric heat to be prior NO 5 Auto heating for units with heat When unit is conn...

Page 5: ...ted and maintained according to these installation and operating instructions and all local codes and ordinances or in their absence with the latest edition of the National Electric Code or CEC for Ca...

Page 6: ...e the wall sleeve The sleeve can not support the load of bricks blocks For existing construction wall opening must be created the proper dimensions are necessary to avoid use of fillers or additional...

Page 7: ...ompressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front 3 Slide the chassis into the wall sleeve until the chassis...

Page 8: ...PLE POWER SOURCES BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE POWER TO THE UNIT FROM THE CIRCUIT BREAKER AND...

Page 9: ...l Displayer On normal operation indicates room temperature When pressing or button indicates setting temperature On time operation indicates timer time On failure operation indicates fault code Warm b...

Page 10: ...TROL The ventilation control lever is located at left side of unit behind front panel NOTE The vent door shipping tape must be removed before using vent control lever See Fig 9 and Fig 10 When set to...

Page 11: ...tions Location of 7 Screws 15 Discharge Air 55 Discharge Air Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the front...

Page 12: ...ings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a 1 4 bubble tilt to the outside and level from right to left Con...

Page 13: ...and operational status including present modes failures airflow restriction warnings operating temperatures and past failures To enter Diagnostic Status Report mode press and hold the down arrows and...

Page 14: ...arting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher t...

Page 15: ...ernet DURATION OF WARRANTY REGISTRATION The warranty begins on the date of purchase by the original consumer The consumer must retain a receipted bill of sale as proof of warranty period Without this...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: