background image

Owner’s Manual -  

Packaged Terminal

7

6

CHASSIS INSTALLATION

1. Remove the cabinet front from the chassis as

described In Front Removal.

2. Insert the chassis into the wall sleeve.

IMPORTANT NOTES:

1. The unit is equipped with a rubber grommet

mounted compressor. These grommets are factory

set and require no adjustment.

2. Check the indoor and outdoor grilles for

obstructions to air flow. The unit must be located

where curtains, furniture, trees, or other objects do

not block the air flow to and from the unit.  If air is

obstructed and/or deflected back into the unit,the

air conditioner compressor may cycle on and off

rapidly.  This could damage  the compressor or

possibly void the warranty.

FRONT REMOVAL

1. Grasp the cabinet front.

3. Slide the chassis into the wall sleeve until the

chassis flanges contact the front edge of the wall

sleeve.

4. Secure the chassis to the wall sleeve using two

screws on each side of the chassis to ensure a

proper seal between the chassis and the wall

sleeve. The screws are supplied in a plastic bag.

Chassis Installation View 2

Chassis Installation View 1

3. Lift the cabinet front off the chassis. Reverse this

procedure to reinstall the cabinet front.

Cabinet Front Removal View 2

2. Pull  the bottom of the cabinet front away from

the chassis until the retaining clips disengage.

Cabinet Front Removal View 1

Screws

(2 on each

side of unit)

Summary of Contents for Comfort-aire Century PTAC07F130A

Page 1: ...0ASC PTAC12F150ASC PTAC15F130ASC PTAC15F150ASC Heat Pump with Electric Heat with seacoast coating PTHP12F130ASC PTHP12F150ASC PTHP15F130ASC PTHP15F150ASC 7 000 15 000 BTUH Cooling w Electric Heat PTAC...

Page 2: ...ING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 CONTENTS UNIT FEATURES 3 INSTALLATION INSTRUCTION 5 WIRING 8 OPE...

Page 3: ...er the compressor turns off the unit will restart when the pressure turns back below 551 psi This protection can effectively avoid the burst and leakage of pipes lessen the system failures and prolong...

Page 4: ...ntrol functions for DIP switches The DIP switches are on main board NO 4 Heating priority ON Heat pump to be prior OFF Electric heat to be prior NO 5 Auto heating for units with heat When unit is conn...

Page 5: ...ted and maintained according to these installation and operating instructions and all local codes and ordinances or in their absence with the latest edition of the National Electric Code or CEC for Ca...

Page 6: ...e the wall sleeve The sleeve can not support the load of bricks blocks For existing construction wall opening must be created the proper dimensions are necessary to avoid use of fillers or additional...

Page 7: ...ompressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front 3 Slide the chassis into the wall sleeve until the chassis...

Page 8: ...PLE POWER SOURCES BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE POWER TO THE UNIT FROM THE CIRCUIT BREAKER AND...

Page 9: ...l Displayer On normal operation indicates room temperature When pressing or button indicates setting temperature On time operation indicates timer time On failure operation indicates fault code Warm b...

Page 10: ...TROL The ventilation control lever is located at left side of unit behind front panel NOTE The vent door shipping tape must be removed before using vent control lever See Fig 9 and Fig 10 When set to...

Page 11: ...tions Location of 7 Screws 15 Discharge Air 55 Discharge Air Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the front...

Page 12: ...ings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a 1 4 bubble tilt to the outside and level from right to left Con...

Page 13: ...and operational status including present modes failures airflow restriction warnings operating temperatures and past failures To enter Diagnostic Status Report mode press and hold the down arrows and...

Page 14: ...arting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher t...

Page 15: ...ernet DURATION OF WARRANTY REGISTRATION The warranty begins on the date of purchase by the original consumer The consumer must retain a receipted bill of sale as proof of warranty period Without this...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: