background image

Owner’s Manual -  

Packaged Terminal

3

2

UNIT FEATURES

This unit has many features which are different than 

those found on conventional PTAC units. The servicer 

must be familiar with these features in order to 

property handle the unit.

LCDI Cords 

- Underwriters Laboratories and the

National Electric Code (NEC) now require power

cords that sense current leakage and can open

the electrical circuit to the unit on units rated at

250 volts or less. In the event that unit does not

operate,check the reset button located on or near

the head of the power cord as part of the normal

troubleshooting procedure.

LCDI power  Cord

Automatic 3-minute compressor lockout 

- After

the compressor cycles off, it will not restart for three

minutes.

Random restart delay 

- To help eliminate power

surges after a power outage, the unit Is equipped

with a two to four minute random restart delay

feature. Whenever the unit is plugged In with the

master switch turned on and the mode switch set in

the cool or heat mode, a random restart will occur.

Indication LEDs - 

The control panel has LEDs that

correspond to fan  operation and to Indicate unit

status. The LEDs next to the selections ON/OFF,

FAN,  COOL, and HEAT indicate which operational

mode Is active.

High Pressure Protection

 - The unit will shut off

automatically when the pressure in the system

is over 638 psi and within 10 minutes, after the

compressor turns off, the unit will restart when the

pressure turns back below 551 psi. This protection

can effectively avoid the burst and leakage of pipes,

lessen the system failures and prolong the service

life.

Failure Tolerance 

- If the unit is  in protection mode

less than 4 times in one hour, the accumulation

times will reset to avoid system failure. Only when

the unit enters protection mode more than 4 times in

one hour will the system fail to restart automatically

and need manual restart.

Standard Physical Dimensions 

- The series PTAC

uses standard dimensions,  42” wide x 16” high x

13-3/4” deep.

Replacement of older units is made easy.

Weather - Protected Electrical Components

-Vital electrical components are protected from the

weather by locating them on the indoor side of the

weather barrier.

Highly Featured Microprocessor  Controls

-  Microprocessor controls are programmed to

interface with the temperature sensors to maximize

comfort conditions for the room occupant.

Thermistors are used to sense small changes in

temperature to give excellent room control and

allow the microprocessor to monitor and react to

changing conditions.

Automatic Emergency Heat  on  Heat  Pump

Units

-Automatically uses electric resistance heat if

the heat pump falls.

High-Temperature Heat Pump Operation

Protection

-Automatically protects the compressor if heat pump

is operated with high indoor coil temperatures.

Power to the outdoor fan and the compressor

are turned off if the indoor coil gets too hot during

heat pump operation to prevent damage to the

compressor.

Summary of Contents for Comfort-aire Century PTAC07F130A

Page 1: ...0ASC PTAC12F150ASC PTAC15F130ASC PTAC15F150ASC Heat Pump with Electric Heat with seacoast coating PTHP12F130ASC PTHP12F150ASC PTHP15F130ASC PTHP15F150ASC 7 000 15 000 BTUH Cooling w Electric Heat PTAC...

Page 2: ...ING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 CONTENTS UNIT FEATURES 3 INSTALLATION INSTRUCTION 5 WIRING 8 OPE...

Page 3: ...er the compressor turns off the unit will restart when the pressure turns back below 551 psi This protection can effectively avoid the burst and leakage of pipes lessen the system failures and prolong...

Page 4: ...ntrol functions for DIP switches The DIP switches are on main board NO 4 Heating priority ON Heat pump to be prior OFF Electric heat to be prior NO 5 Auto heating for units with heat When unit is conn...

Page 5: ...ted and maintained according to these installation and operating instructions and all local codes and ordinances or in their absence with the latest edition of the National Electric Code or CEC for Ca...

Page 6: ...e the wall sleeve The sleeve can not support the load of bricks blocks For existing construction wall opening must be created the proper dimensions are necessary to avoid use of fillers or additional...

Page 7: ...ompressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front 3 Slide the chassis into the wall sleeve until the chassis...

Page 8: ...PLE POWER SOURCES BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE POWER TO THE UNIT FROM THE CIRCUIT BREAKER AND...

Page 9: ...l Displayer On normal operation indicates room temperature When pressing or button indicates setting temperature On time operation indicates timer time On failure operation indicates fault code Warm b...

Page 10: ...TROL The ventilation control lever is located at left side of unit behind front panel NOTE The vent door shipping tape must be removed before using vent control lever See Fig 9 and Fig 10 When set to...

Page 11: ...tions Location of 7 Screws 15 Discharge Air 55 Discharge Air Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the front...

Page 12: ...ings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a 1 4 bubble tilt to the outside and level from right to left Con...

Page 13: ...and operational status including present modes failures airflow restriction warnings operating temperatures and past failures To enter Diagnostic Status Report mode press and hold the down arrows and...

Page 14: ...arting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher t...

Page 15: ...ernet DURATION OF WARRANTY REGISTRATION The warranty begins on the date of purchase by the original consumer The consumer must retain a receipted bill of sale as proof of warranty period Without this...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: