
6
Installation, Operation & Maintenance - HKV Series
HKV Physical Data
Model
084
096
120
150
168
192
240
300
Compressor Quantity
Scroll (1)
Scroll (2)
Factory Charge HFC-410a (oz) [kg] per
circuit
140 [3.97] 156 [4.42] 224 [6.35]
248 [7.03]
140 [3.97] 156 [4.42]
224 [6.35]
248 [7.03]
Blower Motor
Blower Motor Quantity
1
Standard Motor (hp) [kW]
1.0 [.75]
1.5 [1.12]
2 [1.49]
3 [2.24]
2 [1.49]
3 [2.24]
5 [3.73]
5 [3.73]
Large Motor (hp) [kW]
1.5 [1.12]
2.0 [1.49]
3 [2.24]
5 [3.73]
3 [2.24]
5 [3.73]
7.5 [5.60]
7.5 [5.60]
Blower
No. of Blowers
1
2
Blower Wheel Size D x W (in) [cm]
15 x 11 [38.1 x 38.1]
15 x 15 [38.1 x 38.1]
15 x 11 [38.1 x 38.1]
15 x 15 [38.1 x 38.1]
Water Connection Size
FPT (in) [mm]
1-1/2" [38.1]
2" [50.8]
2-1/2" [63.5]
Coax Volume
Volume (US Gallons) [liters]
2.19 [8.28]
2.48 [9.37]
3.46 [13.11]
4.83 [18.29]
6.36 [24.08]
7.39 [27.98]
Condensate Connection Size
FPT (in) [mm]
1" [25.4]
Air Coil Data
Air Coil Dimensions H x W (in) [cm]
36 x 48 [91.4 x 121.9]
2 - 36 x 48 [91.4 x 121.9]
Air Coil Total Face Area (ft
2
) [m
2
]
12 [1.11]
24 [2.22]
Miscellaneous Data
Filter Standard - 1" [25.4mm]
Throwaway (qty) (in) [cm]
(QTY.4) 18 x 25 [45.74 x 63.5]
(QTY.8) 18 x 25 [45.74 x 63.5]
Weight - Operating (lbs) [kg]
880 [399]
930 [422]
960 [435]
1600 [725]
1665 [755]
1695 [769]
Weight - Packaged (lbs) [kg]
895 [406]
945 [429]
975 [442]
1630 [739]
1695 [769]
1725 [782]
All units have grommet compressor mountings, and 1/2" & 1-3/4" electrical knockouts.
For ClimaDry
®
option, add 125 lbs [57 kg] for 084-150 and 250 lbs [114 kg] for 168-300.
Unit Maximum Water Working Pressure
Options
Max Pressure PSIG [kPa]
Base Unit
300 [2,068]
Motorized Water Valve
300 [2,068]
Internal Secondary Pump or ClimaDry
®
145 [999]
Use the lowest maximum pressure rating when multiple options are combined.