Model
Voltage
Code
Voltage
Min/Max
Voltage
Blower
Option
Compressor
Emergency Power Supply
QTY
RLA
LRA
QTY
Pump
FLA
Total
FLA
MCA
Max
Fuse/
HACR
Fan
Motor
FLA
Fan
MCA
Fan
Max
Fuse/
HACR
HKV084
3
208-3-60
197/254
A, B, C
1
23.2
164.0
1
1.10
24.3
30.1
50
4.0
5.0
15
3
208-3-60
197/254
D, E
1
23.2
164.0
1
1.10
24.3
30.1
50
5.0
6.3
15
4
460-3-60
414/506
A, B, C
1
11.2
75.0
1
0.55
11.8
14.6
25
2.0
2.5
15
4
460-3-60
414/506
D, E
1
11.2
75.0
1
0.55
11.8
14.6
25
2.4
3.0
15
5
575-3-60
518/633
A, B, C
1
7.9
54.0
1
0.44
8.3
10.3
15
1.4
1.8
15
5
575-3-60
518/633
D, E
1
7.9
54.0
1
0.44
8.3
10.3
15
1.9
2.4
15
HKV096
3
208-3-60
197/254
A, B, C
1
25.0
164.0
1
1.96
27.0
33.2
50
5.0
6.3
15
3
208-3-60
197/254
D, E
1
25.0
164.0
1
1.96
27.0
33.2
50
6.2
7.8
15
4
460-3-60
414/506
A, B, C
1
12.2
100.0
1
0.98
13.2
16.2
25
2.4
3.0
15
4
460-3-60
414/506
D, E
1
12.2
100.0
1
0.98
13.2
16.2
25
3.1
3.9
15
5
575-3-60
518/633
A, B, C
1
9.0
78.0
1
0.78
9.8
12.0
20
1.9
2.4
15
5
575-3-60
518/633
D, E
1
9.0
78.0
1
0.78
9.8
12.0
20
2.3
2.9
15
HKV120
3
208-3-60
197/254
A, B, C
1
30.1
225.0
1
1.96
32.1
39.6
60
6.2
7.8
15
3
208-3-60
197/254
D, E
1
30.1
225.0
1
1.96
32.1
39.6
60
9.2
11.5
20
4
460-3-60
414/506
A, B, C
1
16.7
114.0
1
0.98
17.7
21.9
35
3.1
3.9
15
4
460-3-60
414/506
D, E
1
16.7
114.0
1
0.98
17.7
21.9
65
4.3
5.4
15
5
575-3-60
518/633
A, B, C
1
12.2
80.0
1
0.78
13.0
16.0
25
2.3
2.9
15
5
575-3-60
518/633
E
1
12.2
80.0
1
0.78
13.0
16.0
25
3.4
4.3
15
HKV150
3
208-3-60
197/254
A, B, C
1
48.1
245.0
1
1.96
50.1
62.1
110
9.2
11.5
20
3
208-3-60
197/254
D, E
1
48.1
245.0
1
1.96
50.1
62.1
110
14.1
17.6
30
4
460-3-60
414/506
A, B, C
1
18.6
125.0
1
0.98
19.6
24.2
40
4.3
5.4
15
4
460-3-60
414/506
D, E
1
18.6
125.0
1
0.98
19.6
24.2
40
7.0
8.8
15
5
575-3-60
518/633
A, B, C
1
14.7
100.0
1
0.78
15.5
19.2
30
3.4
4.3
15
5
575-3-60
518/633
D, E
1
14.7
100.0
1
0.78
15.5
19.2
30
5.2
6.5
15
HKV168
3
208-3-60
197/254
A, B, C
2
23.2
164.0
2
1.10
48.6
54.4
70
6.2
7.8
15
3
208-3-60
197/254
D, E
2
23.2
164.0
2
1.10
48.6
54.4
70
9.2
11.5
20
4
460-3-60
414/506
A, B, C
2
11.2
75.0
2
0.55
23.5
26.3
35
3.1
3.9
15
4
460-3-60
414/506
D, E
2
11.2
75.0
2
0.55
23.5
26.3
35
4.3
5.4
15
5
575-3-60
518/633
A, B, C
2
7.9
54.0
2
0.44
16.7
18.7
25
2.3
2.9
15
5
575-3-60
518/633
D, E
2
7.9
54.0
2
0.44
16.7
18.7
25
3.4
4.3
15
HKV192
3
208-3-60
197/254
A, B, C
2
25.0
164.0
2
1.96
53.9
60.2
80
9.2
11.5
20
3
208-3-60
197/254
D, E
2
25.0
164.0
2
1.96
53.9
60.2
80
14.1
17.6
30
4
460-3-60
414/506
A, B, C
2
12.2
100.0
2
0.98
26.4
29.4
40
4.3
5.4
15
4
460-3-60
414/506
D, E
2
12.2
100.0
2
0.98
26.4
29.4
40
7.0
8.8
15
5
575-3-60
518/633
A, B, C
2
9.0
78.0
2
0.78
19.6
21.8
30
3.4
4.3
15
5
575-3-60
518/633
D, E
2
9.0
78.0
2
0.78
19.6
21.8
30
5.2
6.5
15
HKV240
3
208-3-60
197/254
A, B, C
2
30.1
225.0
2
1.96
64.1
71.6
100
14.1
17.6
30
3
208-3-60
197/254
E
2
30.1
225.0
2
1.96
64.1
71.6
100
21.7
27.1
45
4
460-3-60
414/506
A, B, C
2
16.7
114.0
2
0.98
35.4
39.5
50
7.0
8.8
15
4
460-3-60
414/506
E
2
16.7
114.0
2
0.98
35.4
39.5
50
10.0
12.5
20
5
575-3-60
518/633
A, B, C
2
12.2
80.0
2
0.78
26.0
29.0
40
5.2
6.5
15
5
575-3-60
518/633
E
2
12.2
80.0
2
0.78
26.0
29.0
40
7.7
9.6
15
HKV300
3
208-3-60
197/254
A, B, C
2
48.1
245.0
2
1.96
100.1
112.1
150
14.1
17.6
30
3
208-3-60
197/254
D, E
2
48.1
245.0
2
1.96
100.1
112.1
150
21.7
27.1
45
4
460-3-60
414/506
A, B, C
2
18.6
125.0
2
0.98
39.2
43.8
60
7.0
8.8
15
4
460-3-60
414/506
D, E
2
18.6
125.0
2
0.98
39.2
43.8
60
10.0
12.5
20
5
575-3-60
518/633
A, B, C
2
14.7
100.0
2
0.78
31.0
34.6
45
5.2
6.5
15
5
575-3-60
518/633
D, E
2
14.7
100.0
2
0.78
31.0
34.6
45
7.7
9.6
15
HACR circuit breaker in USA only
All fuses Class RK-5
Table 4D: HKV Electrical Data Dual Point Power with Pump or ClimaDry
®