17
Installation, Operation & Maintenance - HKV Series
Electrical Data
�
WARNING!
�
�
CAUTION!
�
WARNING!
To avoid possible injury or death due to electrical
shock, open the power supply disconnect switch and secure
it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 4A: HKV Electrical Data Standard
Model
Voltage
Code
Voltage
Min/Max
Voltage
Blower
Option
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
HKV084
3
208-3-60
197/254
A, B, C
1
23.2
164.0
4.0
27.2
33.0
50
3
208-3-60
197/254
D, E
1
23.2
164.0
5.0
28.2
34.0
50
4
460-3-60
414/506
A, B, C
1
11.2
75.0
2.0
13.2
16.0
25
4
460-3-60
414/506
D, E
1
11.2
75.0
2.4
13.6
16.4
25
5
575-3-60
518/633
A, B, C
1
7.9
54.0
1.4
9.3
11.3
15
5
575-3-60
518/633
D, E
1
7.9
54.0
1.9
9.8
11.8
15
HKV096
3
208-3-60
197/254
A, B, C
1
25.0
164.0
5.0
30.0
36.3
60
3
208-3-60
197/254
D, E
1
25.0
164.0
6.2
31.2
37.5
60
4
460-3-60
414/506
A, B, C
1
12.2
100.0
2.4
14.6
17.6
25
4
460-3-60
414/506
D, E
1
12.2
100.0
3.1
15.3
18.4
30
5
575-3-60
518/633
A, B, C
1
9.0
78.0
1.9
10.9
13.1
20
5
575-3-60
518/633
D, E
1
9.0
78.0
2.3
11.3
13.6
20
HKV120
3
208-3-60
197/254
A, B, C
1
30.1
225.0
6.2
36.3
43.8
70
3
208-3-60
197/254
D, E
1
30.1
225.0
9.2
39.3
46.8
70
4
460-3-60
414/506
A, B, C
1
16.7
114.0
3.1
19.8
24.0
40
4
460-3-60
414/506
D, E
1
16.7
114.0
4.3
21.0
25.2
40
5
575-3-60
518/633
A, B, C
1
12.2
80.0
2.3
14.5
17.5
25
5
575-3-60
518/633
D, E
1
12.2
80.0
3.4
15.6
18.6
30
HKV150
3
208-3-60
197/254
A, B, C
1
48.1
245.0
9.2
57.3
69.3
110
3
208-3-60
197/254
D, E
1
48.1
245.0
14.1
62.2
74.2
110
4
460-3-60
414/506
A, B, C
1
18.6
125.0
4.3
22.9
27.6
45
4
460-3-60
414/506
D, E
1
18.6
125.0
7.0
25.6
30.3
45
5
575-3-60
518/633
A, B, C
1
14.7
100.0
3.4
18.1
21.8
35
5
575-3-60
518/633
D, E
1
14.7
100.0
5.2
19.9
23.6
35
HKV168
3
208-3-60
197/254
A, B, C
2
23.2
164.0
6.2
52.6
58.4
80
3
208-3-60
197/254
D, E
2
23.2
164.0
9.2
55.6
61.4
80
4
460-3-60
414/506
A, B, C
2
11.2
75.0
3.1
25.5
28.3
35
4
460-3-60
414/506
D, E
2
11.2
75.0
4.3
26.7
29.5
40
5
575-3-60
518/633
A, B, C
2
7.9
54.0
2.3
18.1
20.1
25
5
575-3-60
518/633
D, E
2
7.9
54.0
3.4
19.2
21.2
25
HKV192
3
208-3-60
197/254
A, B, C
2
25.0
164.0
9.2
59.2
65.4
90
3
208-3-60
197/254
D, E
2
25.0
164.0
14.1
64.1
70.3
90
4
460-3-60
414/506
A, B, C
2
12.2
100.0
4.3
28.7
31.8
40
4
460-3-60
414/506
D, E
2
12.2
100.0
7.0
31.4
34.5
45
5
575-3-60
518/633
A, B, C
2
9.0
78.0
3.4
21.4
23.6
30
5
575-3-60
518/633
D, E
2
9.0
78.0
5.2
23.2
25.5
30
HKV240
3
208-3-60
197/254
A, B, C
2
30.1
225.0
14.1
74.3
81.8
110
3
208-3-60
197/254
E
2
30.1
225.0
21.7
81.9
89.4
110
4
460-3-60
414/506
A, B, C
2
16.7
114.0
7.0
40.4
44.6
60
4
460-3-60
414/506
E
2
16.7
114.0
10.0
43.4
47.6
60
5
575-3-60
518/633
A, B, C
2
12.2
80.0
5.2
29.6
32.6
40
5
575-3-60
518/633
E
2
12.2
80.0
7.7
32.1
35.1
45
HKV300
3
208-3-60
197/254
A, B, C
2
48.1
245.0
14.1
110.3
122.3
150
3
208-3-60
197/254
D, E
2
48.1
245.0
21.7
117.9
129.9
175
4
460-3-60
414/506
A, B, C
2
18.6
125.0
7.0
44.2
48.9
60
4
460-3-60
414/506
D, E
2
18.6
125.0
10.0
47.2
51.9
70
5
575-3-60
518/633
A, B, C
2
14.7
100.0
5.2
34.6
38.3
50
5
575-3-60
518/633
D, E
2
14.7
100.0
7.7
37.1
40.8
50
HACR circuit breaker in USA only
All fuses Class RK-5