47
Installation, Operation & Maintenance - HKV Series
HKV 096 Blower Performance
Table Continued on Next Page
All Data is Wet Coil
Airflow
(SCFM)
ESP
Airflow (cfm) at External Static Pressure (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
2400
BHP
0.29
0.34
0.39
0.44
0.49
0.54
0.59
0.64
0.69
0.74
0.79
0.84
0.89
0.94
0.99
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
RPM
403
446
485
527
563
600
633
665
697
726
756
783
811
835
858
Turns Open
5
4
3
6
5.5
4.5
3.5
2.5
1.5
1
5.5
5
4
3.5
3
2500
BHP
0.31
0.34
0.39
0.44
0.49
0.54
0.59
0.64
0.74
0.79
0.84
0.89
0.94
0.99
1.04
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
RPM
411
452
495
532
567
604
636
670
700
729
759
786
813
838
864
Turns Open
5
4
2.5
6
5.5
4
3.5
2.5
1.5
1
5.5
5
4
3
3
2600
BHP
0.34
0.43
0.48
0.53
0.58
0.63
0.68
0.73
0.78
0.83
0.88
0.93
1.03
1.08
1.13
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
RPM
420
460
500
536
570
606
638
671
701
729
759
786
814
839
865
Turns Open
4.5
3.5
2.5
6
5
4
3
2
1.5
1
5
5
4
3
2.5
2700
BHP
0.38
0.43
0.48
0.53
0.59
0.64
0.69
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.14
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
RPM
423
463
504
539
576
609
641
674
703
734
762
788
816
841
867
Turns Open
4.5
3.5
2
5.5
5
4
3
2
1.5
1
5
4.5
4
3
2.5
2800
BHP
0.39
0.44
0.49
0.54
0.64
0.69
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.12
1.22
Sheave/Mtr
B
B
B
A
A
A
A
A
A
C
C
C
C
C
C
RPM
431
474
510
545
581
613
647
677
706
737
764
793
818
843
869
Turns Open
4.5
3
2
5.5
5
4
3
2
1.5
5.5
5
4.5
3.5
3
2.5
2900
BHP
0.44
0.49
0.54
0.59
0.64
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.14
1.19
1.24
Sheave/Mtr
B
B
B
A
A
A
A
A
A
C
C
C
C
C
RPM
440
481
517
551
586
618
651
681
710
740
767
795
821
845
872
Turns Open
4
3
2
5.5
4.5
3.5
2.5
1.5
1
5.5
5
4.5
3.5
2.5
2.5
3000
BHP
0.43
0.49
0.54
0.59
0.64
0.69
0.74
0.84
0.89
0.94
1.04
1.09
1.14
1.19
1.24
1.29
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
RPM
412
455
492
526
563
595
628
658
687
718
745
774
800
826
852
876
Turns Open
5
3.5
2.5
6
5.5
4.5
3.5
2.5
1.5
1.5
6
5
4
3.5
2.5
2
3100
BHP
0.44
0.53
0.59
0.64
0.69
0.74
0.84
0.89
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.39
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
RPM
421
459
499
533
569
600
633
663
691
722
749
777
803
828
854
878
Turns Open
4.5
3.5
2.5
6
5
4
3
2
1.5
1.5
6
4.5
4
3
2.5
2
3200
BHP
0.49
0.54
0.64
0.69
0.74
0.84
0.89
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.39
1.44
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
RPM
441
478
513
549
581
614
644
672
703
730
759
785
810
837
861
887
Turns Open
4
3
2
5.5
5
4
3
2
1.5
1.5
5.5
4.5
4
3
2.5
2
3300
BHP
0.54
0.64
0.69
0.74
0.83
0.89
0.94
0.99
1.04
1.14
1.23
1.29
1.34
1.44
1.49
1.54
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
C
C
C
C
C
E
RPM
456
495
529
561
595
625
656
685
712
741
767
795
820
844
870
893
Turns Open
3.5
2.5
6
5
4.5
3.5
2.5
2
1.5
1
5
4.5
3.5
3
2
2
3400
BHP
0.63
0.69
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.44
1.49
1.54
1.64
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
C
C
C
C
E
E
RPM
471
506
539
574
604
633
664
692
721
747
773
800
825
851
875
898
Turns Open
3
2
5.5
5
4
3.5
2.5
2
1.5
1
5
4
3.5
2.5
2.5
2
3500
BHP
0.64
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.23
1.29
1.34
1.44
1.49
1.54
1.64
1.74
Sheave/Mtr
B
A
A
A
A
A
A
A
A
C
C
C
C
E
E
E
RPM
486
520
555
586
615
647
674
704
730
756
784
808
835
858
883
906
Turns Open
2.5
6
5.5
4.5
4
3
2.5
1.5
1
5.5
4.5
4
3
2.5
2.5
1.5
3600
BHP
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.44
1.49
1.54
1.64
1.74
1.83
Sheave/Mtr
B
A
A
A
A
A
A
A
A
C
C
C
E
E
E
E
RPM
495
528
562
593
624
652
680
708
734
762
787
812
838
861
886
909
Turns Open
2.5
6
5
4.5
3.5
3
2
1.5
1
5.5
4.5
4
3
2.5
2.5
1.5
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level condi
-
tions. Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.