Installation, Operation & Maintenance - HKV Series
Blower Performance Data - Units with ClimaDry
®
(PSC Motor)
Coil Face
Velocity
FPM
HKV with ClimaDry
®
- Additional ESP Loss
HKV084, 096, 168 & 192
In. of Water
HKV120 & 240
In. of Water
HKV300
In. of Water
200
0.14
-
-
225
0.15
-
-
250
0.16
-
-
275
0.17
0.17
-
300
0.18
0.18
-
325
0.19
0.19
0.23
350
0.21
0.21
0.25
375
0.22
0.22
0.26
400
-
0.24
0.28
425
-
0.26
0.30
450
-
0.29
0.33
475
-
-
0.35
500
-
-
0.38
525
-
-
0.41
550
-
-
0.45
575
-
-
0.48
All data is for wet coil.
Example:
Reheat coil loss can be determined from the above table. Coil velocity (FPM) = Airflow (CFM) / Face Area (sq. ft.)
1. HKV120 has a face area of 11 sq. ft. (see physical data table).
2. At 4,200 cfm, coil velocity (FPM) = 4,200 / 11 = 380 FPM
3. From above table, ESP is .22.
4. HKV120 (without ClimaDry
®
) A Drive at .5 ESP, 2.5 turns = 4200 CFM
HKV120 (with ClimaDry
®
) A Drive at .72 ESP, 2.5 turns = 3900 CFM
If drop in CFM is not acceptable, adjust turns to 1.5 for 4200 CFM.
Note - Sometimes drive package must be changed.