Set the system switch to the 

HEAT

position and depress the red

arrow key until the temperature set point is at least 3 degrees
above the room temperature.  The LCD will display a flame icon
to indicate heat.  The heating system should start within several
seconds (the system blower may not come on immediately).

5)

Set the system switch to the 

OFF

position. The system should shut down within several seconds.  The LCD

will again display only the room temperature.  

6)

Set the system switch to the 

COOL

position and depress the

blue arrow key until the temperature set point is at least 3
degrees below the room temperature.  The LCD will display a
snowflake icon to indicate A/C.  The cooling system should start
within several seconds.  WARNING:  Do not perform this test if the outdoor temperature is below 50 F.

7)

Set the system switch to the OFF position.  The system should shut down within several seconds.  The LCD
will again display only the room temperature.  

Programming The User Settings

Temperature Differential 

is factory set at .5 F (0.25 C) for both heating and cooling cycles.  The room tempera-

ture must change .5 F (0.25 C) from the set point temperature before the thermostat will initiate a call for heat or
A/C.  This should be appropriate for most applications.  However, if the system is cycling on and off too frequent-
ly, the setting can be adjusted as follows.

1)

With the system setting in the 

OFF

position, simultaneously

depress the red and blue arrow keys.  The LCD (liquid crystal
display) will display the temperature differential setting.  Using
the red and blue arrow keys set the differential to the desired
setting of .5, 1, or 2 degrees.  The higher the setting, the less
frequently the system will cycle.    

Image shows room temperature
of 70 and HEAT set point of 73.

Image shows room temperature
of 78 and A/C set point of 68.

Image shows temperature
differential setting of  0.5.

70803-IM  12/18/06  2:10 PM  Page 5

Summary of Contents for 70803

Page 1: ...INSTALLATION AND OPERATING INSTRUCTIONS Non Programmable Electronic Thermostat Heat Cool Model 70803 70803 IM 12 18 06 2 10 PM Page 1...

Page 2: ...t the system control to test the installation This will damage the thermostat and void the warranty This thermostat is equipped with automatic compressor protection to prevent damage due to short cycl...

Page 3: ...ntly depressing the bottom locking tab and swinging the back plate up and away 4 Place the back plate against the wall in the desired mounting location with the thermostat wires protruding from the wa...

Page 4: ...the battery compartment door install 2 AA Alkaline batteries included 14 Remove the clear plastic film from the display Testing The New Thermostat WARNING Do not switch the system to cool if the outd...

Page 5: ...ystem should shut down within several seconds The LCD will again display only the room temperature Programming The User Settings Temperature Differential is factory set at 5 F 0 25 C for both heating...

Page 6: ...et ting of 0 30 or 60 seconds 2 When the desired setting is made release the key and the unit will automatically store the setting after 5 seconds Operating The New Thermostat 1 Set the System switch...

Page 7: ...icates this feature has been activated Once the 5 minute delay expires the snowflake will illuminate continuously and the system will be able to re start when called upon NOTE For the purpose of unit...

Page 8: ...Blinking snowflake flame Allow the 5 minute compressor lock out to expire System turns on off Adjust the differential setting on the thermostat too frequently or A high differential decreases cycle r...

Page 9: ...I is displayed Reduce room temperature or allow a newly installed thermostat to acclimate HI indicates a room temperature reading greater than 90 F 32 C LO is displayed Increase room temperature or al...

Page 10: ...10 Wiring Diagrams Typical 5 Wire System RC RH G Y W B O Inst HEAT 24 VAC TRANSFORMER COM HOT COOL 24 VAC TRANSFORMER COM HOT FAN CONTROL COOL CONTROL HEAT CONTROL 70803 IM 12 18 06 2 10 PM Page 10...

Page 11: ...l Single Stage Heat Pump System RC RH G Y W B O Install Jumper Install Jumper C TR REV VALVE COOL ENERGIZED 24 VAC TRANSFORMER COM HOT FAN CONTROL COMPRESSOR CONTROL REV VALVE HEAT ENERGIZED 70803 IM...

Page 12: ...12 Wiring Diagrams Typical 2 Wire Millivolt System RC RH G Y W B O In C TR COM HEAT CONTROL 24 VAC TRANSFORMER HOT 70803 IM 12 18 06 2 10 PM Page 12...

Page 13: ...13 Wiring Diagrams Typical 4 Wire System RC RH G Y W B O Install Jumper C TR HEAT CONTROL COM 24 VAC TRANSFORMER HOT COOL CONTROL FAN CONTROL 70803 IM 12 18 06 2 10 PM Page 13...

Page 14: ...14 70803 IM 12 18 06 2 10 PM Page 14...

Page 15: ...ho purchased the product from a wholesaler For warranty claims consumers should contact the contractor or dealer who installed the thermostat This warranty and Motors Armatures liability does not incl...

Page 16: ...INSTALLATION AND OPERATING INSTRUCTIONS Non Programmable Electronic Thermostat Heat Cool Model 70803 70803 IM 12 18 06 2 10 PM Page 16...

Reviews: