10
Recommended safety devices and wires
Device
EASYAIR W100-200
EASYAIR E100-200
EASYAIR C100-200
1m
1,5m
2m
1m
1,5m
2m
1m
1,5m
2m
Overload and short circuit protection
C6/6kA
B16/3/6kA B20/3/6kA B25/3/6kA
C6/6kA
Differential current protection
IDN=30mA type AC lub A
IDN=30mA type AC lub A
IDN=30mA type AC lub A
IN=16A
IN=40A
IN=16A
Power wire cross-section
3x1,5mm
²
5x1,5mm
²
5x2,5mm
²
5x4,0mm
²
3x1,5mm
²
I
IMPORTANT!
● It is recommended to connect wires to the terminal strip with previously clamped appropriate clip ends.
● Make sure that the space around the place where the air is sucked in by the curtains, as well as around the exhaust grid, is free of any structural elements of the building, which might hamper
the flow of air (e.g. suspended ceilings, covering development, ventilating ducts etc.).
EASYAIR E100 EC
EASYAIR E150-200 EC
EASYAIR W100-200 EC
EASYAIR C100-200 EC
3.4. BUILT INTO A SUSPENDED CEILING
The installation of EASYAIR air curtains in the suspended ceiling is only possible if the appropriate minimum installation dimensions are maintained.
Permitted installation configurations:
IMPORTANT!
Control 0-10VDC: LiYCY 2x0,75 (shielded).
IMPORTANT!
The specification of cables and protections refers to unbounded arrangement of cables (basic execution of the E installation according to the PN-IEC 60364-5-523 standard). One
should always abide by the local laws and recommendations concerning device connection.
EASYAIR is equipped with a terminal strip adjusted to an appropriate thickness of wires.