59
TRTC 220/230/240V series Parameter Descriptions
(All levels are user programmable; some values are interdependent)
220V
230V
240V
Default
Setting
RANGE
Default
Setting
RANGE
Default
Setting
RANGE
40 Slow Detect High Voltage TLV
When input voltage exceeds this level, TRTC 2X0V
series transfers to Battery Mode from either Buck
Mode (when enabled) or Line mode.
275VAC
275VAC
287VAC
287VAC
300VAC
300VAC
On Battery Mode
Line / Buck to Battery
|
|
|
242VAC
253VAC
264VAC
High Voltage Hysteresis
When input voltage returns below this level, TRTC
2X0V series transfers back to Line Mode from
Battery Mode.
Battery to Line
--------------------
265VAC
277VAC
290VAC
( High Lmt - High Hyst )
41 Slow Detect Buck TLV
When input voltage exceeds this level, TRTC 2X0V
series transfers to Buck Mode (when enabled)
reducing the output.
Line to Buck
--------------------
242VAC
253VAC
264VAC
Buck Low Voltage Hysteresis
When input voltage returns below this level, TRTC
2X0V series releases the Buck Mode (when
enabled) and transfers back to the Line Mode.
Buck to Line
--------------------
232VAC
243VAC
254VAC
Normal
--------------------
Boost High Voltage Hysteresis
When input voltage returns above this level, TRTC
2X0V series releases the Boost Mode (when
enabled) and transfers back to the Line Mode.
Boost to Line
--------------------
208VAC
217VAC
226VAC
42 Slow Detect Boost TLV
When input voltage reduces below this level, TRTC
2X0V series transfers to Boost Mode (when
enabled) increasing the output.
Line to Boost
--------------------
198VAC
207VAC
216VAC
Low Voltage Hysteresis
When input voltage returns above this level, TRTC
2X0V series transfers back to the Line Mode from
Battery Mode.
Battery to Line
--------------------
( Low Lmt + Low Hyst )
178VAC
185VAC
193VAC
43 Slow Detect Low Voltage TLV
When input voltage reduces below this level, TRTC
2X0V series transfers to Battery Mode from either
Boost Mode (when enabled) or Line Mode.
168VAC
198VAC
175VAC
207VAC
183VAC
216VAC
Line / Boost to Battery
On Battery Mode
|
|
|
168VAC
175VAC
183VAC
44 High Hysteresis
10VAC
8~12VAC
45 Low Hysteresis
10VAC
8~12VAC
Figure 46